Nortec NHDI User Manual

Page 18

Advertising
background image

- 15 -

Note: The stated times are based on 100% steam

capacity. If the operation is at a lesser capacity, the
time should be extended accordingly. The servicing
intervals are set using the rotary switch “S2” on the
control board.

Drain Cycle

The following indications are provided for the set

flushing interval:

Left: Switch setting on rotary switch “S1”

Right: Set flushing interval

Note: The flushing interval is set on switch “S1” on

the control board.

Note: Water quality conditions resulting in

component failures are not covered under Nortec’s
standard warranty.

The factory settings are based on the following

water conditions when the unit leaves the factory.

Water

Parameters

NHSC

NHDI

Conductivity 0-1500 MicroMhos

0-50 MicroMhos

Hardness

12 grains per gallon
(gpg)

0 grains per gallon
(gpg)

Silica

12 parts per million
(ppm)

0 parts per million
(ppm)

PH

6.5-7.5

7

Chlorides

> 50 parts per mil-
lion (ppm)

> 25 parts per mil-
lion (ppm)

Note: Should you have water conditions above the

stated parameters consult the factory for a new
blowdown setting to help improve your scale
management.

Chlorides – High levels of chlorides will attack

stainless steel. The solution would be to add an in-line
carbon filter that will remove up to 99% of the
chlorides. Consult the factory for additional information
if your water contains high levels of chlorides.

Nortec recommends performing a semi-annual

water analysis to ensure optimal performance.

Stand-by Heating

Stand-by heating activated (”on”) deactivated

(”off”).

Note: If stand-by heating is active the water

temperature in the steam cylinder is constantly kept at
approximately 70ºC (158ºF) by the control board.

Capacity Limitation

The set capacity limitation as a percentage of the

maximum capacity. Press both arrow keys at the
same time and a code will appear. Enter 8808 using
the arrow keys on the keypad and scroll down to the

Position Drain Interval At 100%

S1

Steam Capacity

0

0 Min.

1

720 Min.

2

360 Min.

3

180 Min.

4

120 Min.

5

60 Min.

6

30 Min.

7

20 Min.

8

10 Min.

9

5 Min.

Example:

Position

Duration between
drain cycles

4:120

LCD
Display

Drain
Interval (S1)

NHSC/NHDI
Main Board

NHSC - DI

NHSC(S1)

NHDI (S1)

Model

Setting

Setting

010

4

1

015

4

1

020

5

1

030

6

1

045

7

1

065

8

1

090

8

1

135

8

1

180

8

1

Value Settings

Factory Settings

NOTE: Approximately 1 liter or
0.26 gallons will drain during
these intervals. Drain Water
Cooling will be active during
these intervals to temper the
drain water to 140 degrees F (60
degrees C) or less.

Figure #18

NHSC / NHDI Drain Cycle Parameters

drain cycle

4: 120

stand-by heating

off

power limit [%]

100

Advertising
This manual is related to the following products: