Installation, Receiving equipment, Principal of operation – Nortec Industries MES-U User Manual

Page 3

Advertising
background image

INSTALLATION

RECEIVING EQUIPMENT

1.

Check packing slip to ensure ALL material has
been received.

2.

Inspect box for damage and note on shipping
waybill accordingly.

3.

After unpacking, inspect unit for damage and if
damage is found, advise shipper as soon as
possible.

4.

Inspect unit (humidifier) to ensure it is the correct
model, phase, and voltage. If any are incorrect,
advise the factory or your local representative
immediately.

NOTE: All products are shipped on an F.O.B.

factory basis. Any and all damage, loss, or breakage
claims are to be made directly to the shipping
company.

The NORTEC MES-U electrode humidifier is the

culmination of many years of research and
development in the electrode humidifier industry. This
unit has been built by skilled craftspeople and
thoroughly tested before shipment and should, if the
following instructions are observed, provide many
years of trouble-free operation.

FOR HUMIDIFIERS INSTALLED IN THE CITY

OF LOS ANGELES: A city of Los Angeles approved
spring-loaded double ball CHECK VALVE should be
supplied and installed by the contractor on each of the
potable water inlets to each humidifier.

Recommended valve manufacturer: Watts

Regulator (phone 508-688-1811), model #7, size 3/8”
NPT inlet and outlet.

Each drain line from these humidifiers shall be

routed, without dips or sags, to terminate above the
flood level rim of a City of Los Angeles approved
indirect waste receptor.

No combustible materials shall be placed in the

duct and/or the air plenum.

PRINCIPAL OF OPERATION

When the humidistat calls, the cylinder fills to

110% of the Full Load Amperage (F.L.A.) or to the top
of the cylinder, whichever comes first. See Figure #1.

If it reaches 110% F.L.A. the water heats and boils

away to a level giving 90% F.L.A.

An electronic timer uses the rate of amp fall to

determine the water level. The objective is to
concentrate current-carrying minerals in the cylinder
so that a smaller volume of water is required to
produce the rated steam output.

This achieves the longest life for the disposable

cylinder because of minimal electrode coverage and
use of less energy because the high concentration
allows a minimal drain rate.

When 90% F.L.A. is reached, the fill valve will

open refilling cylinder to 110% F.L.A. On occasion,
the drain valve will also come on if water level is too
low, indicating too high a concentration and the
requirement for a dilution of the water in the cylinder.

If the water reaches top of cylinder before 110%

F.L.A., the fill valve shuts off via the sensor and
fill-boil-fill-boil cycle continues, cycling off the red high
water sensor light until the concentration becomes
high enough to reach 110% F.L.A. The above
described control process will then take over.

- 1 -

Figure #1

Operation Schematic

CONDENSATE RETURN

(OPTIONAL)

1” AIR

GAP

FILL

CUP

1. INLET CHAMBER

3. WATER OVERFLOW

CHAMBER (SAFETY DRAIN

IN CASE OF FILL VALVE/

CONTROL BOARD FAILURE)

STRAINER

FILL

VALVE

TAP

WATER

SUPPLY

DRAIN

CONNECTION

DRAIN

PAN

DRAIN CANAL

(OPEN TO ATMOSPHERE)

DRAIN

VALVE

CYLINDER

1

2

3

2. FILL CHAMBER

STEAM HOSE

ELECTRODES

Advertising