Chimney installation – Napoleon Fireplaces NZ25 User Manual

Page 8

Advertising
background image

WS-415-71 / 09.07.00

8

FIGURE 10 - 4 ELBOWS

FIGURE 9 - 2 ELBOWS

FIGURE 8 - STRAIGHT UP

No Off-Set. Minimum overall chim-
ney height is 15 feet.

Single off-set with two 15°, 30° or
45° elbows. Minimum overall
chimney height is 15 feet.

Double off-set with four 15°, 30° or
45° elbows. Minimum overall chim-
ney height is 15 feet.

CHIMNEY INSTALLATION

This fireplace was tested to CAN/ULC S610-M87 Zero Clearance Fireplace Safety Test Standard. In accordance with this
standard, the unit may be connected to any accepted chimney listed to ULC S-629. The following 7" factory-built chimney
systems may be used:

OLIVER MACLEOD

HT 6103(

FORMERLY

HT3103)

4 - 45

O

4 - 30

O

SECURITY

ASHT

4 - 45

O

4 - 30

O

ICC

EXCEL 2100-2

4 - 45

O

4 - 30

O

ENERGY VENT

HT5103

4 - 45

O

4 - 30

O

GSW

FC

2 - 45

O

& 2-15

O

4 - 30

O

SELKIRK METALBESTOS

SSPLUS

2 - 45

O

2 - 30

O

LISTED TO ULC S610-M87:::::

(45

o

MAX.)

MAXIMUM # OF OFFSETS

MODEL #

MANUFACTURER

(30

o

MAX.)

Installation of all types of factory-built chimney systems is to be in accordance with the chimney manufacturers installa-
tion instructions. An appropriate chimney manufacturers anchor base plate is required in order to initiate the twist lock
mechanism. Air cooled chimney systems are not recommended in colder climates.