Top exit / horizontal termination, 90° h, Definitions elbow vent length values – Napoleon Fireplaces PARK AVENUE GD82PT User Manual

Page 7

Advertising
background image

7

W415-0536 / B / 07.20.06

VERTICAL

RISE IN

FEET

V

T

FIGURE 4

when

(H

T

) < (V

T

)

Simple venting confi guration (only one 90° elbow)

See graph to determine the required vertical rise

V

T

for the

required horizontal run

H

T

.

For vent confi gurations requiring more than one 90° elbow,
the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Example 1:

V

1

= 3 ft

V

2

= 8 ft

V

T

=

V

1

+

V

2

= 3 + 8 = 11 ft

H

1

= 2.5 ft

H

2

= 2 ft

H

R

=

H

1

+

H

2

= 2.5 + 2 = 4.5 ft

H

O

= .03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft

H

T

=

H

R

+

H

O

= 4.5 + 5.4 = 9.9 ft

H

T

+ V

T

= 9.9 + 11 = 20.9 ft

Formula 1:

H

T

< V

T

9.9 < 11

Formula 2:

H

T

+ V

T

< 40 feet

20.9 < 40

Since both formulas are met, this vent confi guration is
acceptable.

FIGURE 5

90°

90°

90°

H

1

V

2

H

2

V

1

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

H

T

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

for the following symbols used in the venting calculations
and examples are:

> - greater than

> - equal to or greater than

< - less than

< - equal to or less than

H

T

- total of both horizontal vent lengths (

H

R

) and offsets

(

H

O

) in feet

H

R

- combined horizontal vent lengths in feet

H

O

- offset factor: .03(total degrees of offset - 90°

*) in

feet

V

T

- combined vertical vent lengths in feet

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°

1.35

16.0

90°

*

2.7

32.0

* the fi rst 90° offset has a zero value and is shown in the
formula as -90°

DEFINITIONS

ELBOW VENT LENGTH VALUES

TOP EXIT / HORIZONTAL TERMINATION