SECTION 4 / SERVICING INSTRUCTIONS

GENERAL LOCATION OF CONTROLS

18

CONTROLS/ADJUSTMENTS/
REPLACEMENTS

TEMPERATURE CONTROLS

The water temperature is controlled by the heater

thermostat on the upper front panel of the heater. The
control center contains an On/Off toggle switch and a
thermostat. The switch functions as a means for turning
the heater on or off.

The thermostat is fitted with a means of limiting the

upper temperature limit below the maximum level. The
knob stop adjustment ring illustrated below is adjust-
able by loosening the set screw, rotating the knobstop
ring to the desired location and retightening the set
screw.

Typical
Comfortable
Spa
Temperature
Range

Typical
Comfortable
Pool
Temperature
Range

Knobstop Ring Set Screw

PRESSURE SWITCH

The pressure switch, or heater actuator, insures

that the heater operates only when the filter pump is in
operation. It is factory set at 1.75 PSI for deck level
installations. When the heater is located below the level
of the spa or pool, it may be necessary to reset the
pressure switch to compensate for the no-flow static
head. If it is necessary to reset the pressure switch, we
recommend the following procedure: see next page
please.

HIGH LIMITS

BYPASS

VALVE

THERMAL

FUSE

TRANSFORMER

IGNITION CONTROL (IID)

BURNERS & PILOT

GAS VALVE

PRESSURE

SWITCH

MANUAL

SWITCH

MANUAL

THERMOSTAT

Fig# 9252