Wiring the Outdoor Sensor

1. There is no connection required if an outdoor sen-

sor is not used in this installation.

2. If using an Outdoor Sensor, connect the wires for

sensor to the terminals marked OUTDOOR SEN

(shown in Fig. 16) in the electrical junction box.

Caution should be used to ensure neither of these

terminals becomes connected to ground.

3. Use a minimum 22 AWG wire for runs of 100 feet

or less, and minimum 18 AWG wire for runs of up

to 150 feet.

4. Mount the outdoor sensor on an exterior surface of

the building, preferably on the north side in an

area that will not be affected by direct sunlight and

that will be exposed to varying weather conditions.

Wiring the Indirect Sensor

1. There is no indirect sensor connection required if

an indirect water heater is not used in the installa-

tion.

2. The XFyre boiler will operate an indirect fired

water heater with either a thermostat type aquas-

tat installed in the indirect tank or a Raypak tank

sensor. When a tank sensor is used, the XFyre

control will automatically detect its presence and a

demand for heat from the indirect water heater will

be generated when the tank temperature falls

below the user settable setpoint by more than the

user selectable offset. The demand will continue

until the sensor measures that the indirect water

heater temperature is above the setpoint.

3. Connect the indirect tank sensor to the terminals

marked DHW SENSOR (shown in Fig. 16) in the

electrical junction box. Caution should be used to

ensure neither of these terminals becomes con-

nected to ground.

Wiring the Optional 0–10 Volt

Building Control Signal

1. A signal from a building management system may

be connected to the XFyre boiler to enable remote

control. This signal should be a 0–10 volt positive

DC signal. When this input is enabled using the

installer menu, a building control system can be

used to control either the setpoint temperature or

the heat output of the XFyre boiler. The control

interprets the 0–10 volt signal as follows. When the

signal is between 0 and 1 volt, the XFyre boiler will

be in stand by mode, not firing. When the signal

rises above 1 volt, the XFyre boiler will ignite. As

the signal continues to rise towards its maximum

of 10 volts, the XFyre boiler will increase either in

setpoint temperature or firing rate, depending on

the setting of screen 17 in the installer menu. See

the Installer Menu section for details on the setting

of screens 16 and 17 for this option.

2. Connect a building management system or other

auxiliary control signal to the terminals marked

+0–10 V and -0–10 V in the electrical junction box

(shown in Fig. 16) Caution should be used to

ensure that the +0–10 V connection does not

become connected to ground.

Wiring the Cascade System

Communication Bus

1. Use standard CAT3 or CAT5 computer network

patch cables to connect the communication bus

between each of the boilers. These cables are

readily available at any office supply, computer,

electronic, department or discount home supply

store in varying lengths.

2. It is recommended that the shortest length cable

possible be used to reach between the boilers and

create a neat installation. Do not run unprotected

cables across the floor or where they will become

wet or damaged. Avoid running communication

cables parallel with, or close to or against, high

voltage (120 volt or greater) wiring. Raypak rec-

ommends that the total maximum length of

communication bus cables not exceed 200 feet.