Regency CLASSIC C34-2 Direct Vent Freestanding Gas Heater

13

VENTING ARRANGEMENTS -

VERTICAL TERMINATION

SYSTEMS FOR RESIDENTIAL MAN-

UFACTURED AND MOBILE HOMES

The shaded area in the diagram below shows all allowable
combinations of straight vertical and offset to vertical runs with
vertical terminations.
Maximum two 45

o

elbows.

All vertical and offset to vertical vent installations require Vent Restrictor
Position "R" (Right). If the vent is ENCLOSED in a chase (min. size 9" x
9") maintain a 1-1/4" clearance to combustibles.

May be installed in Manufactured (Mobile) Homes after first sale.

Venting Arrangements Examples:

Example A)

Venting has a horizontal termination.
A 7 ft. vertical run with 6 ft. horizontal run does not fall within the shaded area, and therefore is an allowable installation with
the factory set vent restrictor position of "C".

Example B)

Offset to Vertical Vent.
A 15 ft. vertical run with 4 ft. horizontal offset distance falls within the shaded area and is an allowable installation with Vent
Restrictor Position "R" (Right).

VENTING ARRANGEMENTS -

HORIZONTAL TERMINATIONS FOR

ALL VENTING SYSTEMS

The shaded areas in the diagram below show all allowable
combinations of vertical runs with horizontal term-inations.
Maximum one 90

O

elbow (two 45

o

elbows equal one 90

o

elbow).

Propane and Natural Gas: Residential, Manufactured

and Mobile Homes Installations

The venting arrangements diagrammed below, have a min. of 75% (flue
loss) efficiency with Fan Off, as required for manufactured homes.
(Actual efficiency may be as high as 85%)

May be installed in Manufactured (Mobile) Homes after first sale.

NOTE: See page 9 for installation instructions for the Vent Restrictor Position.

INSTALLATION

Straight Vertical and Offset to Vertical Terminations

use Vent Restrictor Position "R" (Right)