Systems performance—rsna-b series, Gross systems performance data—rsna-b036, Gross systems performance data—rsna-b042 – Rheem RSNA-B Series User Manual

Page 12

Advertising
background image

12

SYSTEMS PERFORMANCE—RSNA-B SERIES

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

71°F [21.7°C]

67°F [19.4°C]

63°F [17.2°C]

CFM [L/s]

1320 [623]

1200 [566]

1020 [481]

1320 [623]

1200 [566]

1020 [481]

1320 [623]

1200 [566]

1020 [481]

DR

.21

.20

.17

.21

.20

.17

.21

.20

.17

O
U

T

D
O
O
R

D
R
Y

B
U

L

B

T
E

M

P
E
R
A
T
U
R
E

°F

[°C]

75

[23.9]

Total BTUH [kW]
Sens BTUH [kW]
Power

44.4 [13.01]
25.5 [7.47]

2.2

43.6 [12.78]
24.4 [7.15]

2.1

42.4 [12.43]
22.7 [6.65]

2.1

41.3 [12.10]
30.4 [8.91]

2.1

40.6 [11.90]
29.1 [8.53]

2.1

39.5 [11.58]
27.0 [7.91]

2.1

39.6 [11.61]
31.4 [9.20]

2.1

38.9 [11.40]
30.0 [8.79]

2.1

37.8 [11.08]
27.9 [8.18]

2.1

80

[26.7]

Total BTUH [kW]
Sens BTUH [kW]
Power

43.6 [12.78]
25.0 [7.33]

2.3

42.8 [12.54]
23.9 [7.00]

2.3

41.7 [12.22]
22.2 [6.51]

2.2

40.5 [11.87]
29.9 [8.76]

2.3

39.8 [11.66]
28.6 [8.38]

2.3

38.7 [11.34]
26.6 [7.80]

2.2

38.7 [11.34]
30.8 [9.03]

2.3

38.0 [11.14]
29.5 [8.65]

2.3

37.0 [10.84]
27.4 [8.03]

2.2

85

[29.4]

Total BTUH [kW]
Sens BTUH [kW]
Power

42.8 [12.54]
24.5 [7.18]

2.4

42.1 [12.34]
23.4 [6.86]

2.4

40.9 [11.99]
21.8 [6.39]

2.4

39.7 [11.63]
29.4 [8.62]

2.4

39.0 [11.43]
28.1 [8.24]

2.4

38.0 [11.14]
26.1 [7.65]

2.4

38.0 [11.14]
30.3 [8.88]

2.4

37.3 [10.93]
29.0 [8.50]

2.4

36.3 [10.64]
27.0 [7.91]

2.4

90

[32.2]

Total BTUH [kW]
Sens BTUH [kW]
Power

42.0 [12.31]
24.0 [7.03]

2.6

41.3 [12.10]
22.9 [6.71]

2.5

40.2 [11.78]
21.3 [6.24]

2.5

38.9 [11.40]
28.9 [8.47]

2.6

38.3 [11.22]
27.6 [8.09]

2.5

37.2 [10.90]
25.7 [7.53]

2.5

37.2 [10.90]
29.9 [8.76]

2.5

36.5 [10.70]
28.5 [8.35]

2.5

35.5 [10.40]
26.5 [7.77]

2.5

95

[35]

Total BTUH [kW]
Sens BTUH [kW]
Power

41.1 [12.05]
23.5 [6.89]

2.7

40.4 [11.84]
22.4 [6.56]

2.7

39.3 [11.52]
20.9 [6.13]

2.6

38.0 [11.14]
28.4 [8.32]

2.7

37.4 [10.96]
27.1 [7.94]

2.7

36.3 [10.64]
25.2 [7.39]

2.6

36.3 [10.64]
29.3 [8.59]

2.7

35.6 [10.43]
28.0 [8.21]

2.7

34.7 [10.17]
26.0 [7.62]

2.6

100

[37.8]

Total BTUH [kW]
Sens BTUH [kW]
Power

40.0 [11.72]
22.8 [6.68]

2.8

39.3 [11.52]
21.8 [6.39]

2.8

38.2 [11.20]
20.3 [5.95]

2.8

36.9 [10.81]
27.7 [8.12]

2.8

36.3 [10.64]
26.5 [7.77]

2.8

35.3 [10.35]
24.6 [7.21]

2.8

35.2 [10.32]
28.7 [8.41]

2.8

34.5 [10.11]
27.4 [8.03]

2.8

33.6 [9.85]
25.5 [7.47]

2.8

105

[40.6]

Total BTUH [kW]
Sens BTUH [kW]
Power

38.6 [11.31]
22.1 [6.48]

3.0

37.9 [11.11]
21.1 [6.18]

3.0

36.9 [10.81]
19.6 [5.74]

2.9

35.5 [10.40]
26.9 [7.88]

3.0

34.9 [10.23]
25.7 [7.53]

2.9

33.9 [9.94]
23.9 [7.00]

2.9

33.8 [9.91]
27.9 [8.18]

3.0

33.2 [9.73]
26.6 [7.80]

2.9

32.3 [9.47]
24.8 [7.27]

2.9

110

[43.3]

Total BTUH [kW]
Sens BTUH [kW]
Power

36.9 [10.81]
21.1 [6.18]

3.1

36.2 [10.61]
20.1 [5.89]

3.1

35.2 [10.32]
18.7 [5.48]

3.1

33.8 [9.91]
26.0 [7.62]

3.1

33.1 [9.70]
24.8 [7.27]

3.1

32.2 [9.44]
23.1 [6.77]

3.0

32.0 [9.38]
26.9 [7.88]

3.1

31.4 [9.20]
25.7 [7.53]

3.1

30.6 [8.97]
23.9 [7.00]

3.0

115

[46.1]

Total BTUH [kW]
Sens BTUH [kW]
Power

34.6 [10.14]
19.9 [5.83]

3.3

34.0 [9.96]
19.0 [5.57]

3.2

33.1 [9.70]
17.7 [5.19]

3.2

31.5 [9.23]
24.8 [7.27]

3.2

30.9 [9.06]
23.7 [6.95]

3.2

30.1 [8.82]
22.0 [6.45]

3.2

29.7 [8.70]
25.7 [7.53]

3.2

29.2 [8.56]
24.6 [7.21]

3.2

28.4 [8.32]
22.9 [6.71]

3.2

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B042

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

71°F [21.7°C]

67°F [19.4°C]

63°F [17.2°C]

CFM [L/s]

1490 [703]

1350 [637]

1150 [543]

1490 [703]

1350 [637]

1150 [543]

1490 [703]

1350 [637]

1150 [543]

DR

.24

.23

.21

.24

.23

.21

.24

.23

.21

O
U

T

D
O
O
R

D
R
Y

B
U

L

B

T
E

M

P
E
R
A
T
U
R
E

°F

[°C]

75

[23.9]

Total BTUH [kW]
Sens BTUH [kW]
Power

51.1 [14.98]
28.1 [8.24]

2.6

50.2 [14.71]
26.9 [7.88]

2.6

48.8 [14.30]
25.0 [7.33]

2.5

47.7 [13.98]
33.4 [9.79]

2.5

46.9 [13.75]
31.9 [9.35]

2.5

45.6 [13.36]
29.7 [8.70]

2.5

45.2 [13.25]
37.9 [11.11]

2.5

44.3 [12.98]
36.2 [10.61]

2.5

43.1 [12.63]
33.6 [9.85]

2.5

80

[26.7]

Total BTUH [kW]
Sens BTUH [kW]
Power

50.1 [14.68]
27.9 [8.18]

2.7

49.2 [14.42]
26.7 [7.83]

2.7

47.8 [14.01]
24.8 [7.27]

2.7

46.7 [13.69]
33.2 [9.73]

2.7

45.9 [13.45]
31.7 [9.29]

2.7

44.6 [13.07]
29.5 [8.65]

2.6

44.1 [12.92]
37.6 [11.02]

2.7

43.3 [12.69]
36.0 [10.55]

2.7

42.2 [12.37]
33.5 [9.82]

2.6

85

[29.4]

Total BTUH [kW]
Sens BTUH [kW]
Power

49.0 [14.36]
27.5 [8.06]

2.9

48.1 [14.10]
26.3 [7.71]

2.8

46.8 [13.72]
24.5 [7.18]

2.8

45.6 [13.36]
32.8 [9.61]

2.8

44.8 [13.13]
31.3 [9.17]

2.8

43.6 [12.78]
29.1 [8.53]

2.8

43.1 [12.63]
37.2 [10.90]

2.8

42.3 [12.40]
35.6 [10.43]

2.8

41.1 [12.05]
33.1 [9.70]

2.8

90

[32.2]

Total BTUH [kW]
Sens BTUH [kW]
Power

47.9 [14.04]
27.0 [7.91]

3.0

47.0 [13.77]
25.8 [7.56]

3.0

45.8 [13.42]
24.0 [7.03]

2.9

44.5 [13.04]
32.2 [9.44]

3.0

43.7 [12.81]
30.8 [9.03]

3.0

42.5 [12.46]
28.6 [8.38]

2.9

42.0 [12.31]
36.7 [10.76]

3.0

41.2 [12.07]
35.0 [10.26]

2.9

40.1 [11.75]
32.6 [9.55]

2.9

95

[35]

Total BTUH [kW]
Sens BTUH [kW]
Power

46.8 [13.72]
26.3 [7.71]

3.2

45.9 [13.45]
25.1 [7.36]

3.1

44.7 [13.10]
23.4 [6.86]

3.1

43.4 [12.72]
31.5 [9.23]

3.1

42.6 [12.48]
30.1 [8.82]

3.1

41.4 [12.13]
28.0 [8.21]

3.1

40.8 [11.96]
36.0 [10.55]

3.1

40.1 [11.75]
34.4 [10.08]

3.1

39.0 [11.43]
32.0 [9.38]

3.0

100

[37.8]

Total BTUH [kW]
Sens BTUH [kW]
Power

45.6 [13.36]
25.6 [7.50]

3.3

44.8 [13.13]
24.4 [7.15]

3.3

43.6 [12.78]
22.7 [6.65]

3.2

42.2 [12.37]
30.8 [9.03]

3.3

41.5 [12.16]
29.4 [8.62]

3.2

40.4 [11.84]
27.4 [8.03]

3.2

39.7 [11.63]
35.3 [10.35]

3.3

39.0 [11.43]
33.7 [9.88]

3.2

37.9 [11.11]
31.3 [9.17]

3.2

105

[40.6]

Total BTUH [kW]
Sens BTUH [kW]
Power

44.5 [13.04]
24.8 [7.27]

3.4

43.7 [12.81]
23.7 [6.95]

3.4

42.5 [12.46]
22.1 [6.48]

3.4

41.1 [12.05]
30.1 [8.82]

3.4

40.4 [11.84]
28.7 [8.41]

3.4

39.3 [11.52]
26.7 [7.83]

3.3

38.6 [11.31]
34.5 [10.11]

3.4

37.9 [11.11]
33.0 [9.67]

3.4

36.8 [10.79]
30.7 [9.00]

3.3

110

[43.3]

Total BTUH [kW]
Sens BTUH [kW]
Power

43.4 [12.72]
24.2 [7.09]

3.6

42.6 [12.48]
23.1 [6.77]

3.6

41.5 [12.16]
21.5 [6.30]

3.5

40.0 [11.72]
29.4 [8.62]

3.6

39.3 [11.52]
28.1 [8.24]

3.5

38.2 [11.20]
26.1 [7.65]

3.5

37.5 [10.99]
33.9 [9.94]

3.5

36.8 [10.79]
32.4 [9.50]

3.5

35.8 [10.49]
30.1 [8.82]

3.5

115

[46.1]

Total BTUH [kW]
Sens BTUH [kW]
Power

42.3 [12.40]
23.6 [6.92]

3.7

41.6 [12.19]
22.5 [6.59]

3.7

40.4 [11.84]
21.0 [6.15]

3.7

39.0 [11.43]
28.8 [8.44]

3.7

38.3 [11.22]
27.5 [8.06]

3.7

37.2 [10.90]
25.6 [7.50]

3.6

36.4 [10.67]
33.3 [9.76]

3.7

35.7 [10.46]
31.8 [9.32]

3.7

34.8 [10.20]
29.6 [8.67]

3.6

DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input

NOTES:

➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible

capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

[

] Designates Metric Conversions

Advertising