G36D Zero Clearance Direct Vent Gas Fireplace

17

INSTALLATION

The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, with

Rigid

Pipe vent systems for Propane and Natural Gas, as per the diagram 3.

The shaded area in the diagram 3 shows all allowable combinations of straight

vertical and offset to vertical terminations with

Rigid Pipe vent systems for

Propane and Natural Gas. Maximum two 45

o

elbows allowed.

• Vent must be supported at offsets

• Firestops are required at each fl oor level and whenever passing

through a wall.

• Maintain clearances to combustibles as listed in the "Clearances"

section.

Diagram 3