SECTION 3: C

LEARANCES

TO

C

OMBUSTIBLES

5

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 4: ONE SIDE REFLECTOR

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

6

9

63

47

16

23

161

120

TF-160

6

9

70

54

16

23

178

138

TF-200

6

9

77

59

16

23

196

150

TF-250

6

9

83

65

16

23

211

166

TF-300

6

9

86

69

16

23

219

176

TF-350

8

9

88

73

21

23

224

186

TF-380

8

9

88

73

21

23

224

186

A

C

D

B

FIGURE 5: TWO SIDE REFLECTORS

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

6

23

66

23

16

59

168

59

TF-160

6

25

72

25

16

64

183

64

TF-200

6

27

78

27

16

69

199

69

TF-250

6

32

84

32

16

82

214

82

TF-300

6

35

88

35

16

89

224

89

TF-350

8

40

91

40

21

102

232

102

TF-380

8

40

91

40

21

102

232

102

A

C

D

B

FIGURE 6: 45

°

TILT REFLECTOR

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

8

8

60

54

21

21

153

138

TF-160

8

8

66

60

21

21

168

153

TF-200

10

8

74

64

26

21

188

163

TF-250

10

8

78

69

26

21

199

176

TF-300

12

8

84

74

31

21

214

188

TF-350

12

8

85

79

31

21

216

201

TF-380

12

8

85

79

31

21

216

201

Advertising