BRANCH TEMPERATURE - NOT USED

B0 SELECT - # of Branch Sensors Installed

Not used.

RELAY SEQUENCING

HS SELECT - # of Heaters

Enter 1 thru 4 for the number of heaters connected to relay out-

puts 1 thru 4. This allows the RayTemp to correctly sequence heaters and record demand.

SP - SELECT - Stages Per Heater

Enter the number of stages in each heater, from 1 to 4.

SQ - SELECT
Firing Options

Four options for stage sequencing are available. Select number 1, 2,
3, or 4 as follows:

#1

No Lead/Lag: Stage 1 of heater #1 always fires first. The
remaining stages and heaters will fire in order as demand
increases.

#2

24-Hour Rotation: At midnight each day, the firing order is
rotated to the next heater. This distributes the work load
equally among all heaters.

#3

Lead/Lag & Rotate: With this option, heater #1 always fires
first, then the remaining heaters fire in rotation. Since some

flue

designs require heater #1 to fire first; this option meets this
requirement while still providing limited rotation.

US SELECT -

Use 24volt on/off sensing. Do not use.