SINGLE

STAGE

TANKSTAT

STAGE 1

CONNECTION

ATTACH STAGE 1 CONNECTIONS

ON HEATER TO THE SINGLE STAGE

TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE.

2-STAGE

TANKSTAT

STAGE 1

CONNECTION

STAGE 2 CONNECTION OR

STAGE 1 CONNECTION

OF HEATER 2

ATTACH STAGE 1 CONNECTIONS ON HEATER

TO STAGE 1 CONNECTION ON TANKSTAT.

ATTACH STAGE 2 CONNECTIONS OR

STAGE 1 CONNECTION OF HEATER 2

TO STAGE 2 CONNECTIONON TANKSTAT

AS SHOWN IN THE DIAGRAM.

Fig. 15: Single Stage Tankstat

Fig. 16: 2-Stage Tankstat

Heater must be electrically grounded in accordance
with NEC and C22.1(in Canada).

NOTES:
1. Field installed ground to inside of junction box.

2. If any of the original wire as supplied with the

heater must be replaced, it must be replaced with
105°C wire or its equivalent.

Venting

General

Definition of Appliance Categories

Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.

Category I. A heater which operates with a non-posi-
tive vent static pressure and with a vent gas
temperature that avoids excessive condensate pro-
duction in the vent.

Category II. A heater which operates with a non-posi-
tive vent static pressure and with a vent gas
temperature that may cause excessive condensate
production in the vent.

Category III. A heater which operates with a positive
vent pressure and with a vent gas temperature that
avoids excessive condensate production in the vent.

Category IV. A heater which operates with a positive
vent pressure and with a vent gas temperature that
may cause excessive condensate production in the
vent.

See Table H for appliance category requirements for
the Hi Delta.

Determination of Appliance
Category for Venting Purposes and
Venting Arrangements

CAUTION: Proper installation of flue venting is criti-
cal for the safe and efficient operation of the heater.

NOTE: For additional information on appliance
categorization, see appropriate ANSI Z21 Standard
and the NFGC (U.S.), or B149 (Canada), or
applicable provisions of local building codes.

WARNING: Contact the manufacturer of the vent
material if there is any question about the appliance
categorization and suitability of a vent material for
application on a Category III or IV vent system.
Using improper venting materials can result in
personal injury, death or property damage.