Spe cifications, English – Rackmount Solutions Enterprise Series User Manual

Page 16

Advertising
background image

15

English

SPE

CIFICATIONS

&

Acceptable input voltage

Input voltage (on-line operation)

Output voltage

Nominal input frequency

Input protection

Frequency limits (on-line operation)

Transfer time

Maximum load

On-battery output voltage

On-battery frequency

On-battery waveshape

Protection

Surge energy rating

(one time, 10/1000 us waveform)

Surge current capability

(one time, 8/20 us waveform)

Surge response time

Surge voltage let-through

(percentage of applied ANSI

C62.41 Cat. A +/-6kV test waveform)

Noise filter

Battery Type-Spill proof, maintenance free,

user replaceable, sealed lead-acid

Typical battery life

Typical recharge time

Operating temperature

Storage temperature

Operating and storage relative humidity

Operating elevation

Storage elevation

Electromagnetic immunity

Audible noise at 1 m (3 ft.)

Size (H x W x D) in Rackmount and

Desktop Configuration

Weight - Net (Shipping)

NOTE: 230Vac Specs Shown In ( ) 500VA 750VA 1100VA 1500VA 2300VA 3200 VA

Default 117 (225) Vac / User selectable at 108,113.117 (215,225,235) Vac

50 or 60 Hz, +/-.5 Hz, unless synchronized to utility during brownout

True Sine Wave

Overcurrent and short circuit protected, latching shutdown on overload

3 to 6 years, depending on the number of discharge cycles and ambient temp.

2 to 5 hours from total discharge

<5%

<1%

0 - 164 (0 - 290) Vac

75 - 164 (150 - 290) Vac

105 - 128 (210 - 250) Vac

50 or 60 Hz, autosensing

Resettable circuit breaker

50 or 60 Hz, +/-6Hz

<2 ms typical

500VA

300W

750VA

450W

1500VA

900W

2300VA

1380W

3200VA

1920W

500 J (440J)

6.5 kAmps total

500 J (440J)

13 kAmps total

0 ns (instantaneous) normal mode; <5 ns common mode

<5%

<0.5%

0 to 40 degrees C (+32 to 104 degrees F)

-15 to +45 degrees C (+5 to +113 degrees F)

0 to 95%, non-condensing

0 to +3,000 m (0 to + 10,000 ft)

0 to +15,000 m (0 to +50,000 ft)

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

<45 dBA

3.5 x 17 x 16"

(8.9 x 43.2 x 40.7) cm

5.25 x 17 x 16"

(13.4 x 43.2 x 40.7) cm

UL1778, CSA 22.1, CE EMC, CE SAFETY, TUV

Normal and common mode EMI/RFI suppression

Two 12 V

4.5 Ah

Two 12 V

7.2 Ah

10 Base-T surge protection
let-through (as a percentage of an
applied +/-6 kV 1.2/50 us, 500

Telephone line surge protection let-through
(as a percentage of an applied +/-6 kV
1.2/50 us, 500 a 8/20 us test)

Safety and approvals

EMC Verification

FCC Class B certified

Four 12 V

12 Ah

Four 12 V

4.5 Ah

1100VA

660W

Four 12 V

7.2 Ah

Four 12 V

12 Ah

43(49)lb

52(58)lb

57(62)lb

74(80)lb

88(94)lb

95(101)lb

19.5(22)Kg

23.5(26)Kg

25.5(28)Kg

33.5(36)Kg

40(42.5)Kg

43(45.5)Kg