Reliance Water Heaters 317775-000 User Manual

Page 18

Advertising
background image

18

A gas line of sufficient size must be run to the water heater. Consult

the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA

54) or the Natural Gas and Propane Installation Code (CAN/CSA

B149.1) and your gas supplier concerning pipe size.
There must be:

• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of gas control valve to help prevent

dirt and foreign materials from entering the gas control valve.

• A flexible gas connector or a ground joint union between the shut

off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water

heater. Use a soapy water solution, not a match or open flame. Rinse

off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resistant

to the action of petroleum [Propane (L.P.)] gases.
The appliance and its gas connection must be leak tested before

placing the appliance in operation.
The appliance and its individual Shut-off valve should be disconnected

from the gas supply piping system during any pressure testing of that

system at test pressures in excess of 1/2 pound per square inch (3.5

kPa). It should be isolated from the gas supply piping system by closing

its individual manual Shut-off valve during any pressure testing of the gas

supply piping system at test pressures equal to or less than 1/2 pound

per square inch (3.5 kPa).
Connecting gas piping to the gas control valve of water heater can be

accomplished by either of two methods shown in Figures 12 and 13.

fIGure 12. Gas pIpInG wIth

fleXIBle connector.

fIGure 13. Gas pIpInG wIth all

BlacK Iron pIpe to Gas control.

sedIMent traps

A sediment trap should be installed as close to the inlet of the water

heater as practical at the time of water heater installation. The

sediment trap should be either a tee fitting with a capped nipple in

the bottom outlet or other device recognized as an effective sediment

trap. If a tee fitting is used, it should be installed in conformance with

one of the methods of installation shown in Figures 12 and 13.

Contaminants in the gas lines may cause improper operation

of the gas control valve that may result in fire or explosion.

Before attaching the gas line be sure that all gas pipe is clean

on the inside. To trap any dirt or foreign material in the gas

supply line, a drip leg (sometimes called a sediment trap) must

be incorporated in the piping. The drip leg must be readily

accessible. Install in accordance with the “Gas Piping” section.

Refer to the current edition of the National Fuel Gas Code (ANSI

Z223.1/NFPA 54) or the Natural Gas and Propane Installation

Code (CAN/CSA B149.1).

FIGURE 14.

fIllInG the water heater

Advertising