Setting the 1771-sdn node address -6, Setting the 1771-sdn node address – Rockwell SoniCrafter DEVICENET 1771-SDN User Manual

Page 58

Advertising
background image

Publication 1771-6.5.132 - June 2000

4-6 Configuring the DeviceNet Network

Setting the 1771-SDN Node Address

Once the devices are uploaded, their node addresses appear to the
right of their icons. For the example application, the 1771-SDN
scanner module should have a node address of “0” (or “00”). If you
need to change a module’s node address, use the following
procedure.

If “00” appears to the right of the 1771-SDN icon and you do not need
to change the node address or baud rate of any device, skip the
remainder of this section and go to “Configuring the I/O Devices” on
page 4-9.

TIP

RSNetWorx for DeviceNet performs a one-shot
browse when you go online or choose the browse
feature. The software will poll for devices once and
display the results. If a node which was online later
goes offline, there will be no “live” indication in
RSNetWorx. You must manually perform a browse to
detect the missing node.

To perform the browse, press the

button.

TIP

You can use this procedure to change the node
address of other devices on the network (e.g., the
Photoeye). You can also change the network data
rate (baud rate) of some devices. Power must be
cycled for baud rate changes to take effect.

IMPORTANT

The network must not be active when performing
node commissioning on the 1771-SDN module. Make
sure the processor is in Program mode.

(Note that this applies only to the 1771-SDN. You
may commission other devices with the processor in
Run mode.)

Advertising