SECTION 10: WIRING

Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an energy
management system. Section 10.1 illustrates the
connection for heaters controlled by a line voltage
thermostat.

For heaters on a low voltage thermostat, See Page
44, Section 10.2
. Heaters must be grounded in
accordance with applicable codes: United States:
Refer to National Electrical Code

®

NFPA 70 - latest

revision; Canada: Refer to Canadian Electrical Code
CSA C22.1 Part I - latest revision.

If any of the original internal wiring must be replaced,
it must be replaced with wiring materials having a
temperature rating of at least 105°C and 600 volts.

10.1 Line Voltage Thermostat Wiring

DANGER

Electrical Shock Hazard

Disconnect electric before service or

maintenance.

Heater must be connected to a properly

grounded electrical source.

Failure to follow these instructions can

result in death or electrical shock.

L1
L2

Gnd.

N

H

Gnd.

N

H

Gnd.

Additional

Burners

120 V-60 Hz

Supply Circuit

Line Voltage Thermostat

Burner 1

Burner 2

Maximum 5 Burners

Per Thermostat