Caution, Danger – Reliance Water Heaters 317686-000 User Manual

Page 16

Advertising
background image

16

discharge opening must not be blocked or reduced in size under any

circumstances. Excessive length, over 30 feet (9.14 m), or use of

more than four elbows can cause restriction and reduce the discharge

capacity of the valve.

No valve or other obstruction is to be placed between the

Temperature-Pressure Relief Valve and the tank. Do not connect

discharge piping directly to the drain unless a 6” (15.2 cm) air gap is

provided. To prevent bodily injury, hazard to life, or property damage,

the relief valve must be allowed to discharge water in adequate

quantities should circumstances demand. If the discharge pipe is

not connected to a drain or other suitable means, the water flow

may cause property damage.

CAUTION

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

Water Damage Hazard

t&p valve discharge pipe requirements:

• Should not be smaller in size than the outlet pipe size of the valve, or

have any reducing couplings or other restrictions.
• Should not be plugged or blocked.
• Should not be exposed to freezing temperatures.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the

Temperature-Pressure Relief Valve and the discharge pipe.
• Must terminate a maximum of six inches above a floor drain or external

to the building. In cold climates, it is recommended that the discharge

pipe be terminated at an adequate drain inside the building.
• Should not have any valve or other obstruction between the relief

valve and the drain.

DANGER

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

The Temperature-Pressure Relief Valve must be manually operated at

least twice a year. Caution should be taken to ensure that (1) no one

is in front of or around the outlet of the Temperature-Pressure Relief

Valve discharge line, and (2) the water manually discharged will not

cause any bodily injury or property damage because the water may be

extremely hot. If after manually operating the valve, it fails to completely

reset and continues to release water, immediately close the cold water

inlet to the water heater, follow the draining instructions in this manual,

and replace the Temperature-Pressure Relief Valve with a properly

rated/sized new one.

note: The purpose of a Temperature-Pressure Relief Valve is to

prevent excessive temperatures and pressures in the storage tank.

The T&P valve is not intended for the constant relief of thermal

expansion. A properly sized thermal expansion tank must be installed

on all closed systems to control thermal expansion, see Closed Water

Systems and Thermal Expansion on page 14 and 15.

If you do not understand these instructions or have any questions

regarding the Temperature-Pressure Relief Valve call the

toll free number listed on the back cover of this manual for

technical assistance.

hIGh altItude InstallatIon

This heater is approved for operation up to 5,300 feet (1,615 m)

without alteration. High altitude models are available from the factory

for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079

m). For elevations above 10,100 feet (3,079 m) the input rating

should be reduced at the rate of 4 percent for each 1,000 feet (305

m) above sea level which requires replacement of the burner orifice

in accordance with National Fuel Gas Code (ANSI Z223.1/NFPA 54).

Contact your local gas supplier for further information.

Failure to replace standard orifice with a high altitude orifice when

installed above 10,100 feet (3,079 m) could result in improper and

inefficient operation of the appliance, producing carbon monoxide

gas in excess of safe limits, which could result in serious injury or

death. Contact your gas supplier for any specific changes which

may be required in your area.

Gas pIpInG

Fire and Explosion Hazard

Do not use water heater with any

gas other than the gas shown on

the rating plate.

Excessive pressure to gas control

valve can cause serious injury or death
Turn off gas lines during installation.

Contact qualified installer or

service agency.

Make sure the gas supplied is the same type listed on the model

rating plate. The inlet gas pressure must not exceed 14 inch water

column (3.5 kPa) for natural and propane gas (L.P.). The minimum

inlet gas pressure shown on the rating plate is that which will permit

firing at rated input.
All gas piping must comply with local codes and ordinances or with the

National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass

tubing and fittings (except tin lined copper tubing) should not be

used.
If the gas control valve is subjected to pressures exceeding 1/2 psi

(3.5 kPa), the damage to the gas control valve could result in a fire

or explosion from leaking gas.
If the main gas line Shuttoff serving all gas appliances is

used, also turn “off” the gas at each appliance. Leave all

gas appliances shut “off” until the water heater installation

is complete.

Advertising
This manual is related to the following products: