Model

30

45

60

75

100

125

150

175

200

225

250

300

350

400

Total Input

[Btu/h] x [1000]

30

45

60

75

100

125

150

175

200

225

250

300

350

385

Total Output

[Btu/h] x [1000]

24.6

36.9

49.2

61.5

82

102.5

123

143.5

164

184.5

205

246

288.6 315.7

Efficiency

82% - All Models

Number of Burners

2

3

4

5

6

7

7

8

9

10

11

12

14

14

Gas Connection

[in]

3

/

8

3

/

8

½

½

½

½

½

½

½

¾

¾

¾

¾

¾

Inlet Pressure

[in wc] NG Min.

5 - All Models

LPG Propane Min.

12 - All Models

NG & LP Propane Max.

14 - All Models

Electrical Supply

115 V / 60 Hz / 1 Ø - All Models

Full Load Amps @ 115 V

3.0

3.0

4.1

4.1

5.8

5.8

7.1

7.1

10.6

10.6

10.6

11.6

11.6

11.6

Air Volume

[CFM]

691

691

1376

1376

1902

1902

2245

2245

3716

3716

3716

4663

4663

4663

Recommended Maximum

Mounting Height

[ft]

12

12

15

15

20

20

20

20

25

25

25

30

30

30

Number of Axial Fans

1

1

1

1

1

1

1

1

1

1

1

2

2

2

Axial Fan Diameter

[in]

10

10

16

16

16

16

16

16

19.7

19.7

19.7

16

16

16

Horsepower

.06

.06

.08

.08

.2

.2

.2

.2

.3

.3

.3

.4

.4

.4

Fan Motor Amps @ 115 V

1.8

1.8

2.6

2.6

4.3

4.3

4.3

4.3

4.7

4.7

4.7

8.6

8.6

8.6

Fan Motor RPM

1630

1630

1030

1030

1175

1175

1200

1200

1085

1085

1100

1155

1155

1155

Fan Motor Type

SP

SP

SP

SP

PSC

PSC

PSC

PSC

PSC

PSC

PSC

PSC

PSC

PSC

Flue Size

[in]

4 - All Models

Combustion Air Size

[in]

4

4

4

4

4

4

4

4

4

4

4

5

5

5

Weight

[lb]

65

70

85

90

105

110

205

225

255

265

270

355

375

375

Printed in U.S.A.

UHASNA

5M 1106 Rev. A

Roberts-Gordon, LLC

1250 William Street

P.O. Box 44

Buffalo, NY 14240-0044 USA

Telephone: 716.852.4400

Fax: 716.852.0854

Toll Free: 800.828.7450

www.rg-inc.com

European Office:

Roberts Gordon Europe Limited

Telephone: +44(0) 1902 494425

Fax: +44(0) 1902 403200

Important Notice

The equipment described in this Data Sheet is suitable for most commercial and industrial heating applications. However, in certain environments,

particularly where there is a chlorinated atmosphere (e.g. near degreasing plant or other solvent processes) or a particularly dusty atmosphere, specialist

advice should be sought at the design stage. Roberts-Gordon reserves the right to alter product specification details without notice.

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON

®

products must be performed by a contractor qualified in the installation and service of products sold

and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON

®

manuals and all applicable governmental authorities

pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a

qualified contractor annually inspect your ROBERTS GORDON

®

products and perform service where necessary, using only replacement parts sold and sup-

plied by Roberts-Gordon, LLC.

Further Information:

Applications, engineering and detailed guidance on systems design, installation and product performance is available through

ROBERTS GORDON

®

representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

This product is not for residential use.
This document is intended to assist licensed professionals in the exercise of their professional judgement.

© 2006 Roberts-Gordon, LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means

– graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval systems – without written

permission of Roberts-Gordon, LLC.

Combat

®

UHA-Series Technical Data

Advertising