Roberts Gorden CTH2-125 User Manual

Page 26

Advertising
background image

CTH2-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

20

Step 6.3.2 Coupling and Tube Assembly (Continued)

Step 6.4 Turbulator Installation

10

'

± 1

'

(3 m ± .25 m)

Total Overall
Tube Length

7

'

6" ± 1

'

(2.3 m ± .25 m)

Model

Tube Length Minimum

CTH2-40

10' (3 m)

CTH2-60

20' (6 m)

CTH2-80

20' (6 m)

CTH2-100

30' (9 m)

CTH2-125

40' 12 m)

CTH2-150

50' (15 m)

CTH2-175

60' (18 m)

T

w

is

t

Pull String

Tab

Fold tab around outside
of tube nearest to the vent to hold turbulator
in place. Where a vent sleeve
is used, do not fold tab.

Turbulator
Section

Turbulator
Adapter

Turbulator Section
(stainless) used in CTH2-40
heaters must be in the section of
tube nearest to the burner.

Description

Part Number

Turbulator Adapter

03051503

Turbulator Section

03051504

Turbulator Section (stainless)

03051505

Tube

91409XXX

Turbulator Installation

Model

Tube Section

CTH2-40

1st 10' Section

CTH2-60

2nd 10' Section

CTH2-80

2nd 10' Section

CTH2-100

3rd 10' Section

CTH2-125

N/A

CTH2-150

N/A

CTH2-175

N/A

Turbulator must be installed in
the last standard section of
tube. Turbulator is not required
on the CTH2-125/150/175.