On-board diagnostic center, Diagnostic information – Raypak MVB 504 User Manual

Page 6

Advertising
background image

On-Board Diagnostic Center

Raypak’s MVB comes equipped with a microprocessor-controlled diagnostic control center that displays its information on a 2x20 character LCD
display in plain English. This control monitors system safeties, ignition faults and system status, while storing up to 16 reported faults. Raypaks
diagnostic center monitors the fault outputs of the Fenwal ignition control. Converting the Fenwal’s flashing lights into real English fault codes
that anyone can understand. The control is also equipped with a SPDT dry contact relay output that is switched anytime a safety fault occurs.
This can be used for a heater alarm or a BMS safety interface.

CA

TEGOR

Y

I*

BOILERS

(TYPE

H)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

40°F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

GPM

⌬P FT

GPM

⌬P FT

504

25

1.1

34

100

11.3

8

42

2.7

28

1.4

N/A

N/A

754

32

1.7

40

100

13.8

13

63

6.0

42

2.9

32

1.7

1104

46

4.1

40

113

18.6

16

92

13.3

62

6.7

46

4.1

1504

63

8.0

40

113

22.2

22

N/A

N/A

84

13.3

63

8.0

2004

84

16.0

40

113

27.2

30

N/A

N/A

112

26.9

84

16.0

CA

TEGOR

Y

I*

W

A

TER

HEA

TERS

(TYPE

WH)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

GPM

⌬P FT

504

50

2.8

17

100

11.3

8

N/A

N/A

28

1.4

754

50

3.5

25

100

13.8

13

64

6.1

42

3.0

1104

60

6.3

30

113

18.6

16

90

12.6

60

6.3

1504

82

12.6

30

113

22.2

22

N/A

N/A

82

12.6

2004

109

25.5

30

113

27.2

29

N/A

N/A

109

25.5

CA

TEGOR

Y

IV

BOILERS

&

W

A

TER

HEA

TERS

(TYPE

H

&

WH)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

40°F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

⌬T °F

GPM

⌬P FT

GPM

⌬P FT

GPM

⌬P FT

503

25

†

1.1

35

100

11.3

9

43

2.8

29

1.4

N/A

N/A

753

33

†

1.9

40

100

13.8

13

65

6.4

43

3.1

33

1.9

1003

43

‡

3.7

40

113

18.6

15

87

12.0

58

6.0

43

3.7

1253

54

‡

6.2

40

113

22.2

19

109

20.9

73

10.2

54

6.2

1503

65

‡

9.5

40

113

25.5

23

N/A

N/A

87

16.0

65

9.5

1753

76

‡

13.4

40

113

27.2

27

N/A

N/A

101

22.5

76

13.4

2003

87

‡

15.2

40

116

30.2

30

N/A

N/A

116

31.9

87

18.9

6

*Category I with vertical vent, category III with horizontal venting and no extractor.
† Minimum flow 50GPM for WH hot water supply.
‡ Use 30° column as minimum flow for hot water supply.

Boiler Only

Diagnostic Information

Safety Faults

Ignition Control Faults

•

Condensate Drain

•

Low Air

•

Manual High Limit

•

Flame- No CFH

•

Auto High Limit

•

Ignition Lockout

•

Low Water Cut-off

•

Low HSI Current

•

Vent Pressure

•

Low 24VAC

•

High Gas Pressure

•

Internal Control Fault

•

Low Gas Pressure

•

Controller Alarm

•

Flow Switch

•

Blower Switch

•

Factory Option

•

External Interlock

•

Cold Water Run