Emi and environmental type tests, Ruggedswitch, Rs940g – RuggedCom RS940G User Manual

Page 5

Advertising
background image

www.RuggedCom.com

5

RuggedSwitch

®

RS940G

RuggedSwitch

®

RS940G

8-Port Managed Gigabit Ethernet Switch, 128-bit Encryption

EMI and Environmental Type Tests

Environmental Type Tests

Test

Description

Test Levels

Severity Levels

IEC 60068-2-1

Cold Temperature

Test Ad

-40°C, 16 Hours

N/A

IEC 60068-2-2

Dry Heat

Test Bd

+85°C, 16 Hours

N/A

IEC 60068-2-30

Humidity (Damp Heat, Cyclic)

Test Db

95% (non-condensing), 55¡C , 6

cycles

N/A

IEC 60255-21-1

Vibration

Tests Fc

2g @ (10 - 150) Hz

Class 2

IEC 60255-21-2

Shock

Tests Ea

30g @ 11mS

Class 2

IEC 61850-3 EMI TYPE TESTS

TEST

Description

Test Levels

Severity Levels

IEC 61000-4-2

ESD

Enclosure Contact

+/- 8kV

4

Enclosure Air

+/- 15kV

4

IEC 61000-4-3

Radiated RFI

Enclosure ports

20 V/m

x

IEC 61000-4-4

Burst (Fast Transient)

Signal ports

+/- 4kV @ 2.5kHz

x

D.C. Power ports

+/- 4kV

4

A.C. Power ports

+/- 4kV

4

Earth ground ports

3

+/- 4kV

4

IEC 61000-4-5

Surge

Signal ports

+/- 4kV line-to-earth, +/- 2kV line-to-line

4

D.C. Power ports

+/- 2kV line-to-earth, +/- 1kV line-to-line

3

A.C. Power ports

+/- 4kV line-to-earth, +/- 2kV line-to-line

4

IEC 61000-4-6

Induced (Conducted) RFI

Signal ports

10V

3

D.C Power ports

10V

3

A.C. Power ports

10V

3

Earth ground ports

3

10V

3

IEC 61000-4-8

Magnetic Field

Enclosure ports

40 A/m continuous, 1000 A/m for 1 s

N/A

IEC 61000-4-29

Voltage Dips & Interrupts

D.C. Power ports

30% for 0.1s, 60% for 0.1s, 100% for 0.05s

N/A

A.C. Power ports

30% for 1 period, 60% for 50 periods

N/A

IEC 61000-4-11

100% for 5 periods, 100% for 50 periods

2

N/A

IEC 61000-4-12

Damped Oscillatory

Signal ports

2.5kV common, 1kV diff. mode@1MHz

3

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

3

A.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

3

IEC 61000-4-16

Mains Frequency Voltage

Signal ports

30V Continuous, 300V for 1s

4

D.C. Power ports

30V Continuous, 300V for 1s

4

IEC 61000-4-17

Ripple on D.C. Power Supply

D.C. Power ports

10%

3

IEC 60255-5

Dielectric Strength

Signal ports

2kVac (Fail-Safe Relay output)

N/A

D.C. Power ports

1.5kV DC

N/A

A.C. Power ports

2kVac

N/A

IEC 60255-5

H.V. Impulse

Signal ports

5kV (Fail-Safe Relay output)

N/A

D.C. Power ports

5kV

N/A

A.C. Power ports

5kV

N/A

IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS

Test

Description

Test Levels

Severity Levels

IEEE C37.90.3

ESD

Enclosure Contact

+/- 8kV

N/A

Enclosure Air

+/- 15kV

N/A

IEEE C37.90.2

Radiated RFI

Enclosure ports

35 V/m

N/A

IEEE C37.90.1

Fast Transient

Signal ports

+/- 4kV @ 2.5kHz

N/A

D.C. Power ports

+/- 4kV

N/A

A.C. Power ports

+/- 4kV

N/A

Earth ground ports3

+/- 4kV

N/A

IEEE C37.90.1

Oscillatory

Signal ports

2.5kV common mode @1MHz

N/A

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

N/A

A.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

N/A

IEEE C37.90

H.V. Impulse

Signal ports

5kV (Fail-Safe Relay output)

N/A

D.C. Power ports

5kV

N/A

A.C. Power ports

5kV

N/A

IEEE C37.90

Dielectric Strength

Signal ports

2kVac

N/A

D.C. Power ports

1.5kV DC

N/A

A.C. Power ports

2kVac

N/A

Notes:

1. Only applicable to functional earth connections separated from the safety earth connection.

2. Class 2 refers to “Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions”)