3 complete the start-up – Roberts Gorden UHA SERIES 200 User Manual

Page 27

Advertising
background image

SECTION 10: O

PERATION

AND

M

AINTENANCE

21

10.2.2 Start-Up the Gas Valve (All Gases)

10.2.2.1 Check Burner Gas Pressure

1. Remove the plug in the outlet (burner) pressure

test point and connect a pressure tap and a
manometer.

2. With the burner firing, measure the pressure on

the manometer. To adjust the burner pressure,
remove the regulator cover from the valve and
turn the regulator adjustment screw to set the
required burner pressure as stated in the
Technical Data Tables for the correct gas and
model on Page 38, Section 15.3.

NOTE:

If the correct burner pressure cannot be

reached, then check the inlet pressure to the valve
with the burner firing. See Technical Data Tables on
Page 38, Section 15.3
for inlet pressure
requirement.
Do not continue to adjust the regulator if the
pressure is not changing.

If the inlet pressure is too low to allow correct burner
pressure setting, then the gas inlet pressure must be
corrected before completing the commission.

Check Gas Rate

1. After burner pressure adjustment, allow the

heater to operate for at least 15 minutes and
then re-check settings. Adjust pressure setting
if necessary.

2. Check gas flow rate at gas meter.

3. Turn off heater and electrical supply.

4. Remove the manometer and refit all covers to

the valve and tighten the screw of the outlet
pressure tap.

10.2.3 Pressure Switch

The pressure switch is factory pre-set for each
model and is not adjustable.
10.2.4 Turning Off the Heater

Set the thermostat to the "OFF" position or lowest
setting and the main burner will stop.
The fan will run until it is stopped automatically by
the fan thermostat.
Do not use a disconnect switch for control of
heater. Disconnect switch will turn off the fan.
Heat exchanger could be damaged. Warranty will
not cover damage to the heat exchanger if
operated improperly. Only use the disconnect
switch for turning off heater for service or during
off-season.

10.2.5 External Controls

External controls may include time switch, interlock
switch, room thermostat and frost thermostat.
Operate each control to ensure that they function
correctly. Set the switches (if fitted) and
thermostat(s) to the users’ requirements.

10.3 Complete the Start-Up

Ensure that all covers are fitted correctly and all test
points are properly sealed.
10.3.1 Instruction to the User

Explain the controls of the heater to the user
including how to turn it on and off, using the controls
fitted on site.
Give this manual to the user.
Ensure that the user is shown and understands the
importance of maintaining clearances to
combustibles and the user instructions on Page 22,
Section 11
through Page 22, Section 11.5 and
all
warnings defined in this manual.

Advertising