TROUBLE SHOOTING


If the meter locks on a particular display, unplug and plug in again to unlock the display. A total reset defaults all scaling
values to zero. To perform this reset, re-apply power with RESET key pressed in.

Factory Channel settings:

To obtain factory preset values simply re-apply power with ^v key pressed in. Factory settings are as follows:
MODEL NO.

MODEL NO.

MODEL NO.

CHANNEL NOS.

DPS3000 Series-P

DPS3000 Series-TC

DPS3000 Series-TH

CHANNEL 1

Millivolt

J T/C

Thermistor

CHANNEL 2

Voltage

Voltage

Voltage

CHANNEL 3

Current

Current

Current

CHANNEL 4-7

Millivolt

J T/C

Thermistor

(Channels 5,6 & 7 for DPS3100 & DPS3200 only)

Factory default settings for voltage, current and millivolt are:

CURRENT

VOLTAGE.

MILLIVOLT

T/C

PARAMETER

INPUT

INPUT INPUT

INPUT


HIGH SCALE

20.000

10.000

100.00

--

LOW SCALE

0.000

0.000

0.000

--

OFFSET

0.00

0.00

0.00

--

TARE

0.000

0.000

0.000

--

ERROR MESSAGES AND SOLUTIONS

ERROR MESSAGES AND SOLUTIONS


ERROR MESSAGE

ERROR CONDITION

SOLUTION


'EE EROR'

The unit was unable to

If the message keeps coming up,

save programmed value

unplug the unit and reapply power.

in EEPROM -- possible

If the unit still displays the error

failure of EEPROM.

message, send it in for repair.
If error message followed by
8.8.8.8.8.8.8.and the revision
number are displayed occasionally,
it is an indication that power

line

is

very

noisy

and

needs

a

line

filter.


'PIO ERR'

Analog to digital conv-

See above

erter

error

or

keyboard

error

'CARD ER'

Too much noise on

1. If message shows occasionally,

input signals or problem

it indicates that input signal s have

with Scanner card.

too much high voltage noise.

Provide

signal

filters.

2. Unplug and plug the meter again

to

recycle

power.

3.

Scanner

card

defective

--

send

in

for repair


'HIGH AC NOISE'

High AC noise on input

1. If message shows occasionally,

signals or incoming AC

it indicates that input signals or

line interfering with the AC line has too much high

operation of the unit

voltage noise.

2. Provide line and signal filters.