179

FINS/TCP Method

Section 7-4

The details of the above frame are shown in the following table.

FINS FRAME SEND
ERROR NOTIFICATION
Command

If an error occurs in the FINS/TCP header of the FINS FRAME SEND com-
mand, this command is used so that an error code will be returned to the node
that sent the FINS FRAME SEND command by the node that detected the
error. When this command is sent, the source node closes the connection.
The node that receives the command must close the connection quickly.

The details of the above frame are shown in the following table.

The following table shows the list of error codes.

CONNECTION
CONFIRMATION
Command

This command is sent when the FINS NODE ADDRESS DATA SEND (CLI-
ENT TO SERVER) command is received from a client with the same IP
address and FINS node address as another client with a connection that is
already established. The client that receives this command will simply destroy
the frames.

Item

Contents (hexadecimal)

Remarks

Header

46494E53

ASCII code: ‘FINS’

Length

00000014 to 000007E4

20 to 2020 bytes: Length of
data after command.

Command

00000002

Error code

00000000

Not used, so does not require
checking by at the receiving
end.

FINS frame

---

From FINS header ICF to end
of data.

Size
(bytes)

4
4
4
4
12 to 2,012 (Refer to 7-2 FINS Frames for details.)

Header

Length

Command

Error code

FINS frame

FINS/TCP header

FINS frame

Item

Contents (hexadecimal)

Remarks

Header

46494E53

ASCII code: ‘FINS’

Length

00000008

8 bytes: Length of data from
command onwards.

Command

00000003

Error code

---

Refer to the following table of
error codes.

Error code

(hexadecimal)

Details

00000000

Normal

00000001

The header is not ‘FINS’ (ASCII code).

00000002

The data length is too long.

00000003

The command is not supported.

Size
(bytes)

4
4
4
4

FINS/TCP header

Header

Length

Command

E rro r code

Advertising