Possible cause 3: The underfl oor heating or radiator valves are

closed.

Action:

1. Open the valves.

Possible cause 4: The fl ow across the heat pump is greater than

the fl ow in the heating system.

Action:

1. Reduce the speed of the heat carrier pump (see

Tripped high pressure switch

) or increase the speed

of the circulation pump for the heating system.
Contact your dealer for help.

Additional heat is now working at its highest
permitted temperature

There is a sensor T9 in the heat pump, which for reasons of safety, stops the
compressor and limits the additional heat to the heat pump if the tempera-
ture of the return water from the heating system becomes too high. The
limit for additional heat lies at approximately 48ºC.

Possible cause 1: The heat setting is set so high that the heating

system’s return temperature is too high.

Action:

1. Reduce the heat curve setting.

Heat carrier pump
(290 A/W)

Circulation pump
for the heating
system (290 A/W)