12. SPECIFICATIONS

11. MULTIDROP CONFIGURATION

In the disabled state (E=0), the multiplexer outputs no current and exhibits a high
Z state. This mode allows the connection of several DRA-RTM-8 units to one PLC's
analog input, by tying their output terminals and the address lines in parallel, and
applying individual Enable lines to select the desired multiplexer by disabling all
but one (see fig 7).

Figure 7.

ANALOG +

ANALOG -

PLC

ANALOG

INPUT

MODULE

ENABLE 1

DISCRETE

OUTPUT

MODULE

ENABLE 2

MSB

LSB

ANALOG INPUTS:

RTD INPUT:

Zero adjustability:

Span adjustability:

Lead Compensation Error:

Max Lead Resistance:

Pt-100 linearization:
CURRENT INPUT

Max Input Current:

Reverse Polarity Protection:

Output Accuracy (Refer to Current Input):
CONTROL INPUTS:

Logic:

Logic Levels:
OUTPUT:
SWITCHING TIME:
INDICATORS:

SUPPLY VOLTAGE:
SUPPLY CURRENT CONSUMPTION:
FUSE:
TEMPERATURE STABILITY:
OPERATING TEMPERATURE:
STORAGE TEMPERATURE:
HUMIDITY:
HOUSING:

Box:

Terminal:
WEIGHT:
DIMENSIONS:

8, Pt-100 Channels

a

=0.00385

8, 0/4-20mA Channels

50 to +200

o

C

50 to 750

o

C

0.025

o

C for 10

W

lead resistance

120

W

two ways

0.1% of span max.

30 mA

Yes

0.1% of span max.
4 Address

1 Enable input

True High or True Low (User selectable)

Low: "0" < 0.5V High: 5 < "1" < 60V
4-20mA, Current Loop
< 20

mSec (into a resistive load)

1 Yellow LED, Power-On indicator

8 Red LEDs, current activity indicators
24 10% Vdc (regulated)
120 mA 10mA
150 mA, Fast Blow (5x20mm)
0.01% of span/1

o

C

0 to 60

o

C (32 to 140

o

F)

-25 to +85

o

C (-13 to 185

o

F)

5 to 95% Relative humidity, non-condensing
Plastic Polycarbonate

According to IP50 DIN 40050

According to IP20 DIN 40050
0.9 Kg. (2.0 lb.)
73Hx200Wx121mmD (2.88"x7.88"x4.76")