CIO Area Allocations

Section 4-3

Note A transceiver is built into the CS1W-ETN11 and CJ1W-ETN11. If this bit turns

ON, the Ethernet Unit has malfunctioned.

Socket Service Request
Switches 1 to 8 (CPU Unit
to Ethernet Unit)

When a socket service request is executed by control switch manipulation, it
is the following bits that are manipulated. For details, refer to 6-2 Using Socket
Services with Socket Service Request Switches
.

UDP Open Request Switch

TCP Passive Open Request Switch

TCP Active Open Request Switch

Send Request Switch

Receive Request Switch

Close Request Switch

7

6

5

4

3

2

1

0

n+19 to n+22

15 14 13 12 11 10

9

8

Bit

Switch

Status

Manipulated

by

Unit operation

Page

8

0

UDP Open Request
Switch

ON

User

UDP socket opened when switch is turned ON.

117 to
122

OFF

Unit

Unit turns OFF switch when open processing has been
completed (i.e., when a connection has been made).

9

1

TCP Passive Open
Request Switch

ON

User

Passive TCP socket opened when switch is turned ON.

OFF

Unit

Unit turns OFF switch when open processing has been
completed (i.e., when a connection has been made).

10

2

TCP Active Open
Request Switch

ON

User

Active TCP socket opened when switch is turned ON.

OFF

Unit

Unit turns OFF switch when open processing has been
completed (i.e., when a connection has been made)

11

3

Send Request
Switch

ON

User

Send processing executed when switch is turned ON.
(The protocol (TCP/UDP) is determined when the
socket is opened.)

OFF

Unit

Unit turns OFF switch when send processing has been
completed.

12

4

Receive Request
Switch

ON

User

Receive processing executed when switch is turned
ON.
(The protocol (TCP/UDP) is determined when the
socket is opened.)

OFF

Unit

Unit turns OFF switch when receive processing has
been completed.

13

5

Close Request
Switch

ON

User

Close processing executed when switch is turned ON.
(The protocol (TCP/UDP) is determined when the
socket is opened.)

OFF

Unit

Unit turns OFF switch when close processing has
been completed.

14

6

(Not used.)

---

---

---

---

15

7

(Not used.)

---

---

---

---

Advertising