LV860 LEVEL SENSOR

7. Minimum sensor
• Turn the potentiometer screw clockwise until the LED extinguishes. Then

slowly turn counterclockwise (+) until the LED indicates.
Adjust the screw a further full turn clockwise (-) to compensate for any
tolerance.

8. Maximum sensor
• Turn the potentiometer screw clockwise until the LED indicates. Then

slowly turn counterclockwise (+) until the LED extinguishes.
Adjust the screw a further full turn counterclockwise (+) to compensate
for any tolerance.

9. Replace and tighten the female plug.
10. Replace the clamping piece and bushing in the female plug.
11. Tighten the cable gland nut (PG9).
The Level Sensor is now connected, adjusted and ready for operation.

5 - Operating Difficulties

Problem:

The level sensor fails to operate correctly.

Solution:

- Drop medium level below the sensor.
- Remove the level sensor.
- Clean the sensor probe carefully.

▼ The level sensor may be steam-cleaned.