Installation - electronic (0-5v, Output only) – Omega Engineering FPR 200 User Manual

Page 6

Advertising
background image

„ Apply the DC supply voltage directly across the sensor wires. If

the LED does illuminate, the load is either: too great of imped-

ance or an open circuit. If the LED does not illuminate, the sen-

sor's lead wires or circuit are defective.

6. The installation should be complete.

Installation - Electronic (0-5V

DC

Output Only)

1. Connect the red wire (pin 1 for units with the electronic disconnect

option) from the sensor to the positive terminal of the 12-35 VDC

power supply.

2. Connect the black wire from the transmitter (pin 2 for units with the

electronic disconnect option) to the negative terminal of the 12-35

VDC power supply.

3. Connect the green wire from the transmitter (pin 3 for units with

electronic disconnect) to the (+) 0-5 V

DC

input of the data acquisi-

tion device. This connection may be labeled "Voltage Input" or

"Analog Input" on some devices.

4. If applicable, connect the negative side of the power supply to the

negative side of the pulse input.

5. Apply power to the system.

6. If everything is operating correctly, the green LED will illuminate

brightly and the data acquisition device should show an increase in

flow rate as fluid starts flowing through the sensor.

If data acquisition device does not show an increase in flow rate:

„ check wiring terminations for good connections

„ verify that the LED is illuminated

„ verify that the DC supply voltage is between 12 and 35 V

DC

(6)