EN-16

‹

Before Power Up

The following points should be checked carefully before the power is switched on.

•

Check if the power supply meets the inverter specification.

•

Check if the power supply cables are tightly connected to the right terminals (L1, L2, L3).

•

Check if the motor cables are tightly connected to the right terminals on the inverter side (U, V,
W) as well as on the motor side.

•

Check if the braking unit / braking resistor is connected correctly.

•

Check if the Inverter control circuit terminal and the control device are wired correctly.

•

Set all Inverter control circuit terminals to OFF.

•

When a PG card is used, check if it is wired correctly.

‹

Display after Power Up

After normal power up without any problems the operator display shows the following messages

When a fault has occurred or an alarm is active a fault or alarm message will appear. In this case,
refer to

page 21, Troubleshooting

.

‹

Autotuning

Autotuning sets motor parameters automatically when using Open Loop or Closed Loop Vector con-
trol, when the cable length is long or the installation has changed.

„

Setting the Autotuning Mode

One of the following three autotuning modes can be set.

•

Rotating autotuning

•

Non-rotating autotuning

•

Non-rotating autotuning for line-to-line resistance only

Rotating Autotuning (T1-01

=

0)

Rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 0,
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The
Inverter will operate the motor for approximately 1 minute and set the required motor parameters
automatically.

Non-rotating Autotuning (T1-01

=

1)

Non-rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 1,
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The
inverter will supply power to the non-rotating motor for approximately 1 minute and some of the

Display for normal
operation

The frequency reference monitor is dis-
played in the data display section.

Display for fault operation

A fault or alarm message is shown on the
display.
The example shows a low voltage alarm.

Fre

qu

ency Ref

-DRIVE-

U1-02=50.00Hz

U1-0

3

=10.05A

Rdy

U1-

01

=50.00Hz

-DRIVE-

UV

DC B

us

Undervolt