Wiring – Toshiba ETB004Z User Manual
Page 9
 
E6581341
8
2.2. Wiring
When conducting wiring, follow the instructions below.
• Use shield wire for control signal line and ground the unit with shield wire 
 (Use twisted pair shield cable for wiring of the analog monitor output.) 
• Never bind the signal line and main circuit connection wire together. 
• Fix the communication cables after connected. 
Terminal Block
Applicable wire size
The wire length of
peel off the end
Using screwdriver
(The blade tip)
Tightening
torque
TB1
0.2 to 2.5 mm
2
About
7mm
0.6mm thickness
and 3.5mm width.
0.5 to 0.6 N
・
m
TB2 to TB4
0.2 to 1.5mm
2
About
5mm
0.4mm thickness
and 2.5mm width.
0.22 to 0.25 N
・
m
< Input/output terminal interface >
Terminal
symbol
Function Electrical
specification Internal
circuit
R2A 
R2B 
R2C
Relay contact 
point output 
Configuration of 1C contact point
250Vac - 2A (cosφ=1)
250Vac - 1A (cosφ=0.4) 
30Vdc - 1A 
R2A
R2B
R2C
Ry
LI5 
LI6 
LI7 
LI8 
Contact point 
input Changeover 
of sink or source 
No voltage contact input 
 24Vdc - 5mA 
Sink input(common voltage 24V) 
 ON :less than 10Vdc 
 OFF :16Vdc or more 
Source input
ON :11Vdc or more 
OFF :less than 5Vdc 
Note: 
Even when an external power supply 
is used (in sink logic mode i.e. when 
SINK(PLC) is selected), connect the 
reference potential-side (0V side) 
cable from the power supply to the CC 
terminal. 
 
 
 
 
 
24V power supply
24Vdc power output (when SW is 
in any position other than PLC) 
24V internal output terminal 
 24Vdc - 60mA max 
PLC/
P24
Common terminal 
for external 
power supply 
If SW is turned to the PLC position, 
this terminal can be used as a 
common terminal when an external 
power supply is used. 
SINK Logic(SW =SINK(INT))
SW
2.2k ohm
2.2k ohm
CC
LI5
LI6
LI7
LI8
SOURCE
P24/
PLC
SINK(PLC)
SINK
(INT)
P24
SINK Logic (SW =SINK(PLC))
SW
2.2k ohm
2.2k ohm
CC
LI5
LI6
LI7
LI8
SOURCE
P24/
PLC
SINK(PLC)
SINK
(INT)
P24
SOURCE Logic (SW =SOURCE)
SW
SOURCE
2.2k ohm
P24/
PLC
2.2k ohm
CC
LI5
LI6
LI7
LI8
SINK(PLC)
SINK
(INT)
P24
Lan current signal. 
Chose low current contacts to 
avoid poor attaching.