Toshiba PROFIBUS-DP PBDP-110 User Manual
Page 10
 
9
Global Control Functions
•
Freeze mode: Input (monitor) data values are held constant within the PBDP-110
until the next “freeze” command or an “unfreeze” command is 
received. Used primarily for synchronized monitoring of multiple 
Profibus nodes. 
•
Sync mode:
Output (control) data values are held constant within the PBDP-
110 until the next “sync” command or an “unsync” command is 
received. Used primarily for synchronized control of multiple 
Profibus nodes. 
•
Clear_Data:
All output (control) data values are cleared to “0”.
 
 
Network Watchdog 
A network watchdog function is always operating within the PBDP-110. In the event 
of a disconnection from the Profibus network or loss of the network master, the 
PBDP-110 can automatically switch any attached drives over to local control (if 
selected at time of unit commissioning). 
 
 
Indicators 
•
1 green LED is provided to indicate when the PBDP-110 has achieved the 
DATA_EXCHANGE state with the Profibus network master. This serves as a 
convenient indicator that the Profibus master and PBDP-110 are configured 
properly and are exchanging data. 
•
1 green LED on the MMI interface port. The context is application-specific, 
but under normal operation blinks at a 0.5Hz rate as a “heartbeat” indicator. 
Also indicates data transfer when used with the Flashloader programming 
utility. 
•
1 green LED on each of the Channel A and Channel B drive connectors, 
which indicate that the port is receiving power from the corresponding drive. 
 
 
Profibus Network Connector 
The network interface is a standard DB9 female connector with the following signals 
provided: 
 
Pin
Number Function In/Out
3
Profibus network “B” (positive) data line
In/out
4
RTS signal – direction control for fiber optic network 
interface 
Out
5
DGND – power supply ground internally connected to the 
interface board’s isolated ground 
-
6
VP – power supply +5v internally connected to the 
interface board’s isolated P5. 
-
8
Profibus network “A” (negative) data line
In/out
9
RTS signal ground reference – internally connected to the 
interface board’s isolated ground 
-
1, 2, 7
No connection
-