The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 4

Advertising
background image



I. General Information

A.

INSPECT SHIPMENT carefully for any signs of

damage.

1. ALL EQUIPMENT is carefully manufactured,

inspected and packed. Our responsibility ceases

upon delivery of crated boiler to the carrier in good

condition.

2. ANY CLAIMS for damage or shortage in shipment

must be filed immediately against the carrier by

the consignee. No claims for variances from,

or shortage in orders, will be allowed by the

manufacturer unless presented within sixty (60)

days after receipt of goods.

B.

LOCATE BOILER in front of final position before

removing crate. See Figures 1A thru 1D.
1. LOCATE so that smoke pipe connection

to chimney will be short and direct. BOILER

IS SUITABLE FOR INSTALLATION ON

COMBUSTIBLE FLOOR. Boiler cannot be

installed on carpeting.

2. FOR BASEMENT INSTALLATION, provide a

solid base, such as a concrete pad, if floor is not

level, or if water may be encountered on floor

around boiler.

3. PROVIDE SERVICE CLEARANCE of at least 24”

on top of boiler for cleaning flueways. Provide at

least 24" on right side of boiler for removal of rear

tankless heater. Provide at least 24” clearance from

front jacket panel for servicing.

4. For minimum clearances to combustible materials.

See Figure 2.

C.

PROVIDE AIR SUPPLY AND VENTILATION to

accommodate proper combustion. If natural ventilation

is inadequate, provide a screened opening or duct from

the boiler room to the outside. The opening or duct

must be sized so the boiler input will not exceed 4,000

BTUH/Sq. In. of free area. If other air consuming

appliances are near the boiler, the air inlet should be

larger. Consult respective manufacturers.

Table of Contents

I. General Information .................................... 

II. Installation Instructions .............................. 8
III. Indirect Water Heater Piping .................... 2
IV. Operating & Service Instructions ............ 2
V. Maintenance and Service Instructions. ... 0
VI. Boiler Cleaning .......................................... 

Trouble Shooting
Carlin 0200 ............................................. 6
Riello 0 Series ....................................... 6
VII. Repair Parts .............................................7
VIII. Appendix
Low Water Cut Off ..................................5
Burner Specifications ............................6