Toshiba MBSB80-225-43 User Manual

Toshiba

Advertising
background image

11.8"

42.4"

Left Side View

30.1"

Front View

TITLE

DRAWING NO.

REV.

NOTES

A

B

C

D

E

F

G

H

I

J

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

150kVA G8000 Series UPS

3-Breaker Maintenance Bypass Panel

MBSB80-225-43

1.0

52C

52M

52L

Maintenance

Bypass Breaker

225 Amp M.L.O.

w/ (1) #6-250kcmil

Lug per Phase (typ)

Front View

(Door Removed)

27.0"

39.3

"

Utility Feed

UPS Bypass
Input Breaker

UPS Output
Breaker

225 Amp Box-

Mounted Neutral w/

(2) #6-250kcmil Lugs

0.5" Dia.

Mounting Hole (4)

To Critical Load

A

B

C

N

Part No.

UPS
KVA

Breaker

Type

Voltage

kAIC rating at

480/600V

UPS Output
Amp Rating

150

MBSB80-225-43

FD

480/600

25/14

180

Enclosure

Box/Trim

Finish

Breakers

Weight

- NEMA 1, Surface-Mount (UL Listed).
- 12-Gauge painted steel, trim held with adjustable clamps; Door equiped
with one 3x5 directory cardholder and Corbin type 15767 Snaplock.
- Beige polyester powdercoat on all surfaces, treated with sealer.
- Cutler-Hammer thermal-magnetic type, 225A frame, 3-pole, trip settings as
shown, supplied with (1) #4-4/0 terminal lug per phase.
- Approximately 190 lbs total.

Feed From Utility

Feed To Critical Load

52C

225AT

52M

225AT

52L

225AT

ST

A

B

C

A

B

C

A

B

C

A

B

C

Feed

from
UPS

Output

Feed to

UPS

Input

N

1) This drawing is for illustration purposes only and is subject to change without notice. TIC
is not responsible for any errors or omissions.

TOSHIBA

INTERNATIONAL CORPORATION

Houston Texas, USA

THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF

TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT

BE REPRODUCED, USED, OR DISCLOSED TO OTHERS

UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.

Drawn by

EO

Date 07/07/04

Approved by

JIS

Date 07/07/04