Heater location, Mounting height, Heater throw - all models – Thomas & Betts LDAP 1200 User Manual

Page 7

Advertising
background image

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 7

10. Heater

Location

Use the clearances in Paragraph 8; the combustion air requirements in Paragraph 9;
the mounting height requirements, throw information, sound data, and location rec-
ommendations below; the weights in Paragraph 11; and the venting requirements in
Paragraph 24 to determine where to suspend the heater.

Mounting Height

Locate the heater so that it is a minimum of 15 feet (4.6M) above the floor and in
compliance with the clearances in Paragraph 8.

WARNING: If touched, the vent pipe and internal heater surfaces
that are accessible from outside the heater will cause burns. Suspend
the heater a minimum of 15 feet (4.6M) above the floor.

CAUTION: Do not locate the heater where it may be exposed to
water spray, rain, or dripping water.

Heater Throw -
All Models

NOTES:

•

X = Distance from “0” to beginning
of floor coverage.

•

Y = Distance from “0” to end of
floor coverage.

•

Length of floor coverage = Y - X.

•

Z = Distance from “0” to the point
where the air velocity drops below
50 feet (15.2M) per minute.

•

Throws listed are with standard
louvers facing one direction and
fully open. Throw pattern changes
with louver angle, 2-way louver
direction, and or optional 4-way
louvers.

Throw (feet and meters)

FIGURE 3 - Model LDAP Air Throw (Heat Mode @ High Speed) - Applies to All Sizes

0 = “Rear” of Heater Discharge

Mounting

Height

Standard Louvers

30° Nozzle

60° Nozzle

X
Y
Z

X
Y
Z

X
Y
Z

Standard
Louvers

30° Nozzle

60° Nozzle

0

X

Y

Z

X

Y

Z

X

Y

Z

20

5

55

134

40

90

146

70

125

158

30

8

53

121

44

86

133

76

119

145

40

12

49

109

47

81

120

N/A

N/A

N/A

50

17

45

96

N/A

N/A

N/A

N/A

N/A

N/A

X

Y

Z

X

Y

Z

X

Y

Z

6.1

1.5

16.8

40.8

12.2

27.4

44.5

21.3

38.1

48.2

9.1

2.4

16.2

36.9

13.4

26.2

40.5

23.2

36.3

44.2

12.2

3.7

14.9

33.2

14.3

24.7

36.6

N/A

N/A

N/A

15.2

5.2

13.7

29.3

N/A

N/A

N/A

N/A

N/A

N/A

M

o

unti

n

g

Hei

g

ht

(Meters

)

Standard Louvers

30° Degree Nozzle

60° Degree Nozzle

Throw (meters)

M

o

unti

n

g

Hei

g

ht

(feet)

Standard Louvers

30° Degree Nozzle

60° Degree Nozzle

Throw (feet)

Advertising