Specifications

OVERVIEW

Amp Capacity

15A at 120V AC

Efficiency

96%

Form Factor

Small tower format

Input Plug Type

NEMA 5-20P-HG

Leakage Current

Less than 100 microamps

Let-through Voltage
(Combination Wave)

L-N: 250V L-G: 250V N-G: 0.5V

Let-through Voltage (Ring
Wave)

L-N: 20V L-G: 20V N-G: 0.5V

Noise Suppression Rating

35-65 DB

Nominal Voltage / Frequency

120V / 60Hz

Output Receptacle Qty / Type

6 NEMA 5-20R-HG

Over Current Protection

1x thermal, 2 pole, 10 amp

Shipping Weight

58.00 lbs. / 26.31 kg

Suppression Joule Rating

1190 (1020 input / 170 output)

Surge Test Conditions

Per ANSI/IEEE C62.41 - IEEE587 Cat. A & B test waveforms

Total Harmonic Distortion

Less than 1%

Transformer Type

Hospital Grade, low impedance transformer-based line isolation transformer

Unit Dimensions (HWD/in.)

7.75 x 8.25 x 12.25

VA / Watt Capacity

1800

INPUT

Input cord length (ft.)

10

Input cord length (m)

3.05

PHYSICAL

Cooling method

Convection

Unit Dimensions (HWD/cm)

19.69 x 20.96 x 31.11

CERTIFICATIONS

Certifications

Tested to UL60601-1

WARRANTY

Product Warranty Period
(Worldwide)

2-year limited warranty