Table PD-1. CFM Capacity Correction Table

Cfm Compared

Cooling

Sensible

To Rated

Capacity

Capacity

Quanitity

Multiplier

Multiplier

-20%

0.970

0.910

-10%

0.985

0.955

DX Cooling

Std

1.000

1.000

+3%

1.005

1.014

+6%

1.009

1.027

-20%

0.970

0.910

-10%

0.985

0.955

Waterside

Std

1.000

1.000

Economizer

+3%

1.005

1.014

+6%

1.009

1.027