Performance data — 60 hz (10–60ton) part load, Performance data — 60 hz, 10–60 ton) part load – Trane CG-PRC007-EN User Manual

Page 27

Advertising
background image

27

CG-PRC007-EN

Performance
Data — 60 HZ

Table PD-18— Part Load Data, ARI Points (10-60 Tons)

Entering Condenser Air Temperature (Degrees F)

Model

95

86.9

84.5

77.7

77.3

72.5

72.3

71.5

Tons Number

100% Load

86% Load

82% Load

71% Load

70% Load

62% Load

62% Load

61% Load

EER

10.0

—

—

—

—

—

—

—

10

CGA 120

2

Capacity (Tons)

8.7

—

—

—

—

—

—

—

KW

Input

10.5

—

—

—

—

—

—

—

EER

9.6

—

—

—

—

—

—

—

15

CGA 180

Capacity (Tons)

13.6

—

—

—

—

—

—

—

KW Input

16.9

—

—

—

—

—

—

—

EER

9.8

—

—

—

—

—

—

15.2

20

CGAF-C20

Capacity (Tons)

17.7

—

—

—

—

—

—

10.7

KW Input

21.6

—

—

—

—

—

—

8.5

EER

9.8

—

—

—

13.8

—

—

—

25

CGAF-C25

Capacity (Tons)

23.1

—

—

—

16.3

—

—

—

KW Input

28.3

—

—

—

14.2

—

—

—

EER

9.8

—

—

—

—

—

—

14.2

30

CGAF-C30

Capacity (Tons)

28.0

—

—

—

—

—

—

17.0

KW Input

34.3

—

—

—

—

—

—

14.4

EER

9.7

—

11.9

—

—

—

15.1

—

40

CGAF-C40

Capacity (Tons)

34.5

—

28.4

—

—

—

21.4

—

KW Input

42.7

—

28.6

—

—

—

17.1

—

EER

9.7

11.3

—

13.5

—

—

—

—

50

CGAF-C50

Capacity (Tons)

43.0

37.2

—

30.6

—

—

—

—

KW Input

53.2

39.4

—

27.2

—

—

—

—

EER

9.7

—

11.9

—

—

15.2

—

—

60

CGAF-C60

Capacity (Tons)

55.4

—

45.7

—

—

34.6

—

—

KW Input

68.6

—

45.9

—

—

27.3

—

—

Table PD-18 Continued — Part Load Data, ARI Points (10-60 Tons) Continued

Entering Condenser Air Temperature (Degrees F)

Model

66.2

65.3

57.4

55

Tons Number

52% Load

51% Load

37% Load

32% Load

EER

13.5

—

—

—

10

CGA 120

Capacity (Tons)

4.6

—

—

—

KW

Input

4.1

—

—

—

EER

13.5

—

—

—

15

CGA 180

Capacity (Tons)

7.1

—

—

—

KW Input

6.2

—

—

—

EER

—

—

—

—

20

CGAF-C20

Capacity (Tons)

—

—

—

—

KW Input

—

—

—

—

EER

—

15.3

—

—

25

CGAF-C25

Capacity (Tons)

—

11.7

—

—

KW Input

—

9.1

—

—

EER

—

—

—

—

30

CGAF-C30

Capacity (Tons)

—

—

—

—

KW Input

—

—

—

—

EER

—

—

—

17.6

40

CGAF-C40

Capacity (Tons)

—

—

—

10.9

KW Input

—

—

—

7.4

EER

—

—

17.0

—

50

CGAF-C50

Capacity (Tons)

—

—

15.9

—

KW Input

—

—

11.2

—

EER

—

—

—

18.3

60

CGAF-C60

Capacity (Tons)

—

—

—

17.8

KW Input

—

—

—

11.7

(10–60 Ton)
Part Load

Notes:
1. Rated in accordance with ARI Standard 550/590-98

- 44 Degrees leaving chilled water temperature
- Constant Evaporator waterflow as determined at full load operation, 95 F ambient, and 10F evaporator temperature drop.
- Entering ambient temperature based on 55F for loads below 33%
- Entering ambient temperature based on 0.60(%load)+35 for loads above 33%
- EER- Energy Efficiency Ratio ( Btu/Watt-hour). Power inputs include compressor, condenser fans and control power.

2. Single phase CGA120B1 model should be re-rated at all operating points using the following factors: 1.08 x KW, 0.92 x EER