Environmental specifications, 2 wiring – Toshiba G7 User Manual

Page 14

Advertising
background image

G7 ASD Multi-Protocol Communication Option and PG Feedback Option Manual

7

4.2 Wiring

•

Use shielded wire for control signals and ground the unit with shielded wire.

•

Applicable wire size for terminal block TB1 is 0.2 to 2.5mm

2

.

•

Strip off the end of the wire by about 5mm.

•

For connecting wires, use a screwdriver that has a blade tip of 0.4mm thickness and 2.5mm width.

•

Tightening torque of the terminal block screws should be 0.22 to 0.25Nm.

•

Never route the signal or communication network lines and main circuit power wires
together
. Separate the signal and communication network lines and the main circuit power wires
by more than 200mm.

•

Use 0.75mm

2

wire for connecting the option’s PGCC terminal to the drive’s CC terminal.

•

Use 0.75mm

2

wire for connecting the option’s ground lug (TB2) to the drive’s G/E terminal.



5. Environmental Specifications

Item Specification

Operating Environment

Indoors, less than 1000m above sea level, do not expose to direct
sunlight or corrosive / explosive gasses

Operating Temperature

-10

∼ +50°C (+14 ∼ +122°F)

Storage Temperature

-40

∼ +85°C (-40 ∼ +185°F)

Relative Humidity

20%

∼ 90% (without condensation)

Vibration

5.9m/s

2

{0.6G} or less (10

∼ 55Hz)

Cooling Method

Self-cooled

Advertising