Disconnect switch - udas only, For location, see figure 18, page 31 – Thomas & Betts UDAP User Manual

Page 34

Advertising
background image

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 34

Trial for Ignition

Call for Heat

Is there a

spark across gap at

ignitor?

Does gas

ignite?

Is there minimum

flame current at the

flame sensor?

Is there

minimum flame current

at the control

module?

Replace control

module.

Check connections to flame

sensor and/or moisture in the

burner assembly.

Is the flame

sensor corroded?

Clean flame

sensor.

Is the sensor

located in flame

correctly?

Replace flame

sesnsor.

Reposition

flame sensor.

Is gas

flowing?

Is the ignitor

position correct in the

gas flow?

Check gas pressure

and supply voltage.

If either are low,

correct and repeat

startup.

Reposition

spark ignitor.

Is there

24VAC at the gas

valve?

Is there 24VAC

from gas valve output on

control module to

chassis?

Check wiring and

connections to

gas valve.

Replace

ignition

control

module.

Replace gas

valve.

Is there

spark voltage at

control?

Check high

voltage wire

continuity.

Is there 24V P1-2

to power control?

Replace

control

module.

Check wiring

and/or 24VAC

transformer output.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

YES

NO

YES

NO

40. Troubleshooting

37. Flame

Rollout
Switch -
Sizes 30-125
only

39. Vent or Vent/

Combustion
Air System

For location, see
FIGURE 18, page 31.

The cause of a flame rollout switch activating must be determined. Activation of
the manually reset flame rollout switch could be caused by one or more of the
following:

• Restricted combustion air inlet or exhaust outlet

in combination with a defective pressure switch

• Building exhaust
• Electrical power interruption during operation

If a flame rollout switch trips, inspect the burner/control compartment for signs of
excessive heat and burned wiring.

If the compartment appears normal, reset by depressing the red button on the
switch. 15 to 20 minutes are required for the switch to cool sufficiently for reset-
ting. A distinct click will be felt when the switch resets. Operate the furnace. If
the flame rollout switch trips again, determine and correct the cause before reset-
ting the switch.
If there is damage to the control compartment, repairs must be made before
resetting the switch.

If it is determined that the flame rollout switch needs replacing, use only the fac-
tory-authorized replacement part that is designed for that size of heater.

38. Disconnect

Switch -
UDAS only

• Restricted or plugged

heat exchanger

• Pressurization of the

heat exchanger

The disconnect switch is located in the sealed electrical box inside the con-
trol compartment with the toggle on the rear of the heater.
If it is determined that the disconnect switch needs replacing, use only the
factory-authorized replacement part that is designed for the heater. Always
replace electrical box cover.

Check the complete system at least once a year. Inspection should include all joints,
seams, concentric adapter box (UDAS), inlet air guard or inlet air cap (UDAS), and
the vent terminal cap. Clean openings. Replace any defective parts.

DSI Integrated Control Module
(Circuit Board) Trial
Troubleshooting
Flowchart