Warnings – Toshiba 1700 User Manual

Page 23

Advertising
background image

T

O

S

H
IB

A

2

3

Description and Resolution

The batteries have less than
30% power remaining. The
warning will continue until either
the batteries become completely
exhausted or AC input power is
restored.

An output current limit warning
is typically a sign of
misapplication. The load may
not be appropriate for UPS
support. For further explanation
contact your Toshiba UPS
service representative at 1-877-
867-8773

(outside the U.S.

call 713-466-0277)

.

The temperature of the UPS
operating environment is too
high. Causes of this condition
include allowing the room
temperature to exceed 104°F
(40°C), a blocked vent or direct
sunlight on the unit. The unit will
transfer to bypass until the
temperature is reduced.

Alarm State

Alarm will
sound for
1-second
at 5-
second
intervals.

Alarm will
sound for
1/2-
second at
1-second
intervals.

Alarm will
sound for
1-second
at 15-
second
intervals.

LED State

Warning/Fault ...Flash
Backup ..............Flash

Warning/Fault ...Flash
80%...................Flash

Warning/Fault ...Flash
100%.................Flash

Display State

Warnings

Warning

Low Battery

Current
Limit (Over
Current)

Ambient
Over Heat