Supply and Motor Lead Wiring and Connections

Only copper conductors should be connected to the compressor motor due to the possibility of

galvanic corrosion as a result of moisture if aluminum conductors are used. Copper conductors are

recommended for supply leads in the starter panel.

Suggested starter panel line- and load-side lug sizes (when lugs are provided) are noted in the

starter submittals. These submitted lug sizes should be carefully reviewed for compatibility with

conductor sizes specifi ed by the electrical engineer or contractor. If they are not compatible, the

electrical engineer or contractor should specify the required lug sizes for the particular application.

Ground lugs are provided in the motor terminal box and starter panel. The motor terminals are

supplied with connection pads that will accommodate bus bars or standard terminal lugs (crimp

type recommended). Terminal lugs are fi eld-supplied. These connection pads provide additional

surface area to minimize improper electrical connections. Also, a 3/8-inch bolt is provided on all

connection pads for mounting the lugs. Figure J-1 illustrates the connection between the motor

connection pads and the terminal lugs.

Shipment and Assembly

All style hermetic centrifugal units ship as a factory assembled, factory tested package, ready to rig

into place on factory supplied isolation pads.