RT318

1

8-channel RTD input

Type RT318

Category

RTD ( Resistance Temperature Detector ) input

Resistance temperature
detectors

Pt100

Measuring method

Three-wire system

Load current

1 mA

Temperature measurement
range

-50

° to +270°C (-58° to +518°F)

Converted data

800 to 4000

Input channel

8 channels / module

Insulation

Photo-coupler insulation (not isolated between the channels)

Conversion rate

400 ms / 8 channels

Resolution

12 bits / 0.025 % ( 0.1

°C / count )

Wire resistance correction
range

Within 4

Overall accuracy

±0.3 % (at 25 °C)

Tepaerature drift

±100 ppm / °C

Internal current consumption

5 Vdc, 600 mA or less

Insulation resistance

10 M

Ω (500 Vdc)

Withstand voltage

500 Vac, 1 minutes ( between internal and external circuits)

Weight 500

g

Internal circuit

In

te

rnal c

ir

c

u

it

Buf

fer

memor

y

5 Vdc

+15V
-15V

0V

AMP

Input

f

ilt

er

1A
1B
1C
1G

PC : Photo-coupler

CH1

CH8

8A
8B
8C
8G

M

u

ltip

lexer

DC/DC

AG

AG

Rref

Rref

ADC

PC

Current source

1 mA

1 mA

Wire break

detection

PC