Specifications, Hardwired models) – Tripp Lite 93-2007 (200106010) User Manual

Page 17

Advertising
background image

17

Specifications

(Hardwired Models)

HARDWIRED MODELS:

APSINT1524

APSINT2012

Weight:

12.7 Kg

17.1 Kg

INVERTER
Continuous power (@ 20° C):

1500 W

2000 W

Surge power (5 seconds):

3000 W

4000 W

Efficiency (Full Load):

89%

87%

Minimum DC Fuse Rating:

90A

370A

DC Input Current @ Nominal V DC

Full Load

70A

192 A

No Load

1.5A*

3 A*

Nominal Input Volts:

24 VDC

12 VDC

DC Input Voltage Range:

20-30 VDC

10-15 VDC

Nominal Output Volts:

230 VAC ±5%

230 VAC ±5%

Nominal Output Frequency:

50† Hz ±.3%

50† Hz ±.3%

BATTERY CHARGER
Charging Capacity DC:

10 A**

60 A

Maximum Cable Length

7 ft.

1 ft.

Acceptance Volts VDC:

Selectable

Selectable

28.8 V**/28.4 V Wet**/Gel

14.4 V**/14.2 V Wet**/Gel

Float Volts VDC (w/gel):

26.6 V (27.2 V)

13.3 V (13.6 V)

Input Voltage AC:

230 V

230 V

Input Current AC:

2.2 A**

7.0 A

LINE VAC OPERATION
Minimum Input AC Volts:

Selectable 144**, 163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC

Maximum Input AC Volts
(Continuous, Charger at Maximum):

Selectable 259** or 264 VAC

Selectable 259** or 264 VAC

Maximum Input Current
(Continuous, Charger at Maximum):

13.0 A

16 A

Input Frequency:

50 Hz ±10%

50 Hz ±10%

Maximum Output AC (Continuous)

6.5 A

8.7 A

Automatic Transfer Time:

4-6 ms

4-6 ms

HARDWIRED MODELS (Cont.):

APSINT2424

APSVRI3636

Weight:

18.5 Kg

25.6 Kg

INVERTER
Continuous power (@ 20° C):

2400 W

3600 W

Surge power (5 seconds):

4800 W

7200 W

Efficiency (Full Load):

89%

88%

Minimum DC Fuse Rating:

220A

130A

DC Input Current @ Nominal V DC

Full Load

112 A

114 A

No Load

1.8 A*

2 A*

Nominal Input Volts:

24 VDC

36 VDC

DC Input Voltage Range:

20-30 VDC

30-45 VDC

Nominal Output Volts:

230 VAC ±5%

230 VAC ±5%

Nominal Output Frequency:

50† Hz ±.3%

50† Hz ±.3%

BATTERY CHARGER
Charging Capacity DC:

30 A

30 A

Maximum Cable Length

3 ft.

4.5 ft.

Acceptance Volts VDC:

Selectable

Selectable

28.8 V**/28.4 V Wet**/Gel

43.2 V**/42.6 V Wet**/Gel

Float Volts VDC (w/gel):

26.6 V (27.2 V)

39.9 V (40.8 V)

Input Voltage AC:

230 V

230 V

Input Current AC:

7.0 A

10.4 A

LINE VAC OPERATION
Minimum Input AC Volts:

Selectable 144**,163, 182 or 201 VAC

Selectable 144**,163, 182 or 201 VAC

Maximum Input AC Volts
(Continuous, Charger at Maximum):

Selectable 259** or 264 VAC

Selectable 259** or 264 VAC

Maximum Input Current
(Continuous, Charger at Maximum):

17.0 A

26.0 A (30.0 A***)

Input Frequency:

50 Hz ±10%

50 Hz ±10%

Maximum Output AC (Continuous)

10.4 A

15.7 A

Automatic Transfer Time:

4-6 ms

4-6 ms

*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming
current.†A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.

200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 17