Connection, Continued, Select the transformer module’s input voltage – Tripp Lite 5kVA User Manual

Page 15: Connect the battery module to the power module, Hardwire the transformer module to your equipment

Advertising
background image

15

Select the transformer module’s input voltage.

Using a screwdriver, remove the panel covering the transformer module’s
Input Voltage Select Switch

. Set the switch to match your facility’s input

voltage. Then, use the power module’s front panel switches to configure input
voltage on the LCD Display (see “Configure your UPS’s input and output” in
the “Power ON/OFF” section on page 14).
IMPORTANT NOTE: if your facility’s input voltage is 200V AC, set the trans-
former module’s switch to 240V AC, but configure the power module to 200V
AC. If your facility’s input voltage is either 208V AC or 240V AC, the trans-
former module and power module settings must match. The factory default
settings for both modules is 208V. See chart below.

Transformer Module

Power Module

Your Facility's

Input Voltage Setting

Input Voltage Setting

Input Voltage

(Rear Panel Switch)

(Front Panel Switches/LCD Display)

240V AC

240V AC

240V AC

208V AC

208V AC

208V AC

200V AC

240V AC

200V AC

Connect the battery module to the power module.

Consult the owner’s manual that came with your battery module. Fully insert
the connector on the end of the battery module’s cable

into the connector on

the rear panel of the power module

. Small sparks may occur; this is normal.

NOTE: the power module does not contain internal batteries and will not start
until a battery module is connected. The battery modules are fully charged prior
to shipping. However, before expecting full backup capability (particularly if
the battery module has been stored for an extended period) after the UPS system
is connected to a utility power source, allow the battery module to recharge for
12 hours. Once the UPS system is in use, it will charge the batteries and maintain
the charge level automatically. If needed, connect additional battery modules in
a daisy-chain with each module’s cable inserted into the previous module’s
connector

.

Connection Combination #5: Power Module (10kVA)
+ Transformer Module (10kVA) + Battery Module(s)

Hardwire the power module to the transformer module.

Using a screwdriver, remove the top of the box

covering the power module’s input

and output terminals. Remove the top of the box

covering the transformer

module’s terminals. With supplied cable, connect the power module’s input and
output terminals to the corresponding terminals on the transformer module’s
“Hardwire Terminal Block for Power Module Connection” in the box’s right
knockout

.

Hardwire the transformer module to your equipment.

Pass a user-supplied cable through the box’s left knockout

and connect it to

the transformer module’s output terminals. See the AC Output Voltage Diagram

to determine which terminal connections will provide voltage appropriate to

your application. Connect the other end of the cable to your equipment.

E

D

C

B

A

M

L

K

J

Connection

continued

NORMAL

BY

PASS

240V A

C

208V A

C

4

5

NORMAL

BY

PASS

5

NORMAL

BY

PASS

1

1

NORMAL

BY

PASS

2

2

4

J

M

L

A

B

C

D

K

Connection Combination #5 continued on next page

120

V

240

V

120

V

208

V

AC OUTPUT VOLTAGE DIAGRAM

G

E

Advertising