Chimney, Chimney height – United States Stove Company 3800PB User Manual

Page 8

Advertising
background image

8

This prevents any amount of condensed or liquid creosote from running down the outside of the

pipe or the stove top. All joints, including the flue collar connection must be secured with three sheet

metal screws to ensure that the sections do not separate.
For the best performance the chimney connector should be as short and direct as possible, with no

more than two 90° elbows. The maximum horizontal run is 36” and a recommended total length of

stovepipe should not exceed 10 feet. Always slope horizontal runs upward ¼” per foot toward the

chimney.
No part of the chimney connector may pass through an attic or roof space, closet or other con-

cealed space, or through a floor ceiling. All sections of the chimney connectors must be accessible

for cleaning. Where passage through a wall or partition of combustible construction is desired, the

installation must conform with NFPA 211 or CAN/CSA-B365, and is also addressed in this manual.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE. DO

NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
This room heater must be connected to a 6” factory built UL 103 HT chimney (ULC S629, in Cana-

da) or a code-approved masonry chimney with a flue liner.

Chimney

A masonry chimney or a listed factory-build chimney must be the required height above the roof and

any other nearby obstructions. The chimney must be at least 3’ (90 cm) higher than the highest

point where it passes through the roof and at least 2’ (60 cm) higher than the highest part of the roof

or structure that is within 10’ (305 cm) of the chimney, measured horizontally.

Chimney Height