INSTALLATION

The following formula can be used to determine the maximum
heater rating per the definition of unconfined space:

BTU/HR = (L1+L2) Ft x (W) Ft x (H) Ft x 1000

50

Consider two connecting rooms with an open area between,
with the following dimensions:(See Fig. 2, Example)

L1=15-1/2 Ft., L2=12 Ft., W=12 ft., H=8Ft

50

=52800 BTU/HR

If there were a door between the two rooms the calculation
would be based only on the room with the heater.

BTU/HR=(15-1/2) x (12) x (8) x 1000

50

=29760 BTU/HR

FIGURE 2.

When installing the appliance directly on carpeting, tile or other combustible
material, other than wood flooring, the appliance must be installed on a metal or
wood panel extending the full width and depth of the appliance.

WARNING

If the area in which the heater may be operated is smaller than that defined as an
unconfined space or if the building is of unusually tight construction, provide
adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, Section 5.3, or applicable local codes.

L2 (12')

L1 (15-1/2')

W (12')

H (8')

Minimum clearances to combustibles:

Top of heater....................................36"
Sides of heater....................................8"
Front of heater..................................42"
Rear of heater.....................................4"

FIGURE 3. Minimum Clearances

36"

8"

8"

4"

42"

Ensure the minimum clearances shown in FIGURE 4 are maintained for
accessibility for purposes of servicing and proper operation. Left and right
clearances are determined when facing the front of the heater.

WARNING

WARNING

Maintain these clearances to
ensure adequate space
around air opening for
proper operation.