Fresh air for combustion - chimney vented boilers, Warning – Ultimate Products PF Series User Manual

Page 10

Advertising
background image

Fresh Air for Combustion - Chimney Vented Boilers

8

WARNING

Be sure to provide enough fresh air for combustion.

Enough air ensures proper combustion and assures that

no hazard will develop due to the lack of oxygen.

You must provide for enough fresh air to assure proper

combustion. The fire in the boiler uses oxygen. It must have a

continuous supply. The air in a house contains only enough

oxygen to supply the burner for a short time. Outside air must

enter the house to replace that used by the burner. Study following

examples 1 and 2 to determine your fresh air requirements.
EXAMPLE 1: Boiler Located in Unconfined Space
If your boiler is in an open area (unpartitioned basement) in a

conventional house, the air that leaks through the cracks around

doors and windows will usually be adequate to provide air for

combustion. The doors should not fit tightly. Do not caulk the

cracks around the windows.
An unconfined space is defined as a space whose volume is not

less than 50 cubic feet per 1,000 Btu per hour of the total input

rating of all appliances installed in the space.
EXAMPLE 2: Boiler Located in Confined Space
A. All Air from Inside the Building: The confined space shall

be provided with two permanent openings communicating

directly with an additional room(s) of sufficient volume so that

the combined volume of all spaces meets the criteria for an

unconfined space. The total input of all combustion equipment

installed in the combined space shall be considered in making

this determination. Each opening shall have a minimum free

area of one square inch per 1,000 Btu per hour of the total

input rating of all combustion equipment in the confined space,

but not less than 100 square inches. One opening shall be

within 12 inches of the top and one within 12 inches of the

bottom of the enclosure. See Figure 5.
Example: Your boiler is rated at 100,000 Btu per hour. The

water heater is rated at 30,000 Btu per hour. The total is

130,000 Btu per hour. You need two grilles, each with 130

square inches of FREE opening. Metal grilles have about 60%

FREE area. To find the louvered area needed, multiply the

FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in. louvered

area). In this example two grilles, each having an 8" x 30"

(240 sq. in.) louvered area would be used. Fig. 5 shows the

grille locations.

B. All Air from Outdoors: The confined space shall be provided

with two permanent openings, one commencing within 12

inches of the top and one commencing within 12 inches of the

bottom of the enclosure. The openings shall communicate

directly, or by ducts, with the outdoors or spaces (crawl or

attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each

opening shall have a minimum free area of one square

inch per 4,000 Btu per hour of total input rating of all

equipment in the enclosure.

2. When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of

one square inch per 4,000 Btu per hour of total input rating

of all equipment in the enclosure.

NOTE

If you use a fireplace or a kitchen or bathroom exhaust

fan, you should install an outside air intake. These devices

will rob the boiler and water heater of combustion air.

3. When communicating with the outdoors through horizontal

ducts, each opening shall have a minimum free area of

one square inch per 2,000 Btu per hour of total input rating

of all equipment in the enclosure.

4. When ducts are used, they shall be of the same cross-

sectional area as the free area of the openings to which

they connect. The minimum dimension of rectangular air

ducts shall be not less than three inches.

¼" Mesh

Screen Btuh

Wood

Louvers Btuh

Metal

Louvers Btuh

3½"

x

12"

144,000

36,000

108,000

8"

x

8"

256,000

64,000

192,000

8"

x

12"

384,000

96,000

288,000

8"

x

16"

512,000

128,000

384,000

Fresh Air

Duct Size

FIG. 5 - AIR OPENINGS FOR CLOSET OR

UTILITY ROOM INSTALLATIONS

Fresh Air Duct Capacities for Ducts Supplying Fresh Air to

boiler in tightly constructed houses. British Thermal Units

per hour input (Btuh)*.

FIG. 6 - FRESH AIR DUCT CAPACITIES

* Based on opening covered by 1/4” mesh screen, wood louvers, or metal louvers

FIG. 7

FRESH AIR DUCT FOR TIGHTLY SEALED HOUSE

Advertising