Warning – Venmar 700 cfm User Manual

Page 8

Advertising
background image

Page 8

Allow the heat recovery core to soak for three

hours in warm water and mild soap. Rinse under a
heavy stream of water.

Fans

Blower wheels and fan housing should be checked

for dirt build-up. If they appear dirty, it may be
necessary to remove the blower assembly and then
vacuum the dust out through the fan mouth. See the
following page for instructions on removing the
blower assembly.

System Operation Check

Verification of all control modes should be

checked to ensure proper operation. Refer to the
Controls Section, Sequence of Operation.

Testing and Replacement of the Damper Actuator

Check damper operation by switching between

LOW - COM or HIGH - COM on the dry contact
terminal or by switching through the modes on the
optional remote wall control. If the damper does not
respond in one or both directions, check all connections.

700 cfm ONLY: Check for 24 volt output between the
White/Red and the White/Orange wires at the damper
motor. If 24 volts can be measured at the damper
motor, the problem is either in the connections, the
defrost relay or the main circuit board.

600/1200 cfm ONLY: (CAUTION: 120VAC) Check
for 120 volt output across the White/Black wires. If
120 volt can be measured at the motor, replace the
motor. If 120 volt cannot be measured at the motor,
check pins J1-9 at the printed circuit board.

Main Circuit Board Replacement

The main circuit board must be replaced if an

electronic problem arises. For example, the unit
suddenly stops, the unit stays in defrost all of the
time or if control functions are not working properly.

Ensure that power is reaching the board. Test the

blower motors and damper actuators for operation
when directly connected to the appropriate power
voltage. If the motor and damper actuators function
normally, replace the main circuit board.

Motor and Blower Removal and Installation

Disconnect power from the unit. To determine if

the fan motor is burned out, disconnect the four-wire
service connector between the motor and cabinet.
Connect the motor directly to a 115 volt power
source with an electrical cable, as follows:

If the motor functions normally, there is a problem

with the wiring connections or the main circuit
board. Check all wiring and replace main circuit
board if necessary.

If the blower does not run, it must be replaced. To

replace the motor, remove the heat recovery core
from the unit. Disconnect the four-wire service connector
from the unit. Remove the fasteners holding the
motor assembly in place. Lift the assembly up and
out, using one hand under the motor and one hand to
steady it. Remove the assembly carefully from the
unit to avoid damage to the insulation, shelf, etc.
Install the repaired motor assembly by following
these instructions in reverse.

600 cfm and 1200 cfm

700 cfm

RED + WHITE

Low speed

BLUE + WHITE

Medium speed

BLACK + WHITE

High speed

REMOVE THESE
2 SCREWS

LOCKING PLATE

CAPACITOR

VD0004A

SERVICE CONNECTOR

THUMBSCREW

VD0001A

WARNING

Hot water and a strong cleaning agent could
damage the polypropylene core. Ensure the core is
returned to the unit in the correct orientation. Use
the sticker as a guide.