Owner’s manual, Installation, Continued – Vanguard Heating VMH3000TN User Manual

Page 13

Advertising
background image

13

104431

OWNER’S MANUAL

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2 psig
will damage heater regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by
either using compressed air or open-
ing main gas valve located on or near
gas meter.

4.

Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

ON

POSITION

OFF

POSITION

Open

Closed

Equipment
Shutoff
Valve

Equipment
Shutoff
Valve

Thermostat Gas
Valve Location

Figure 21 - Equipment Shutoff Valve

Gas Meter

Figure 22 - Checking Gas Joints

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 21).

2.

Pressurize supply piping system by
either using compressed air or open-
ing main gas valve located on or near
gas meter.

3.

Check all joints from gas meter to
equipment shutoff valve (see Figure
22). Apply mixture of liquid soap and
water to gas joints. Bubbles forming
show a leak.

4.

Correct all leaks at once.

Pressure Testing Heater Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 21).

2.

Open main gas valve located on or near
gas meter.

3.

Make sure control knob of heater is in
the OFF position.

4.

Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 22). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater,
pages 14 and 15). Check all other in-
ternal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to
Appliance
, page 14).

8.

Replace front panel.

INSTALLATION

Continued

CHECKING GAS
CONNECTIONS

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming show
a leak. Correct all leaks at once.